Page 16
Modulating Unitary Range
VA-LT206_11292016al
Figure 13: Baffle Installation
INSTALLATION
•
If required for your heater model (refer to Table 1), install the baffle at the end of the heat exchanger.
The small tab on the baffle is folded over the end of the tube and clamped in place by the vent connector
and vent system, (refer to Figure 13).
•
•
Note:
Baffles are always placed at the end of the last heat exchanger tube length, with the exception to
the special configurations (115,000 BTU/H with a 40’ tube length, and 200,000 BTU/H with 50’ and 60’
tube length) refer to Figure 3 for more details.
•
•
Note:
Baffles are either one or two sections (each section is 6' in length). Multiple sections are simply
coupled together. Where stainless and aluminized sections are supplied, always place the stainless steel
section closest to the burner. The easiest installation method is to pull the baffle through the tube using a
long wire.
BAFFLE INSTALLATION
VENT
ADAPTER
BEND TAB
OVER END
OF TUBE
AT 6 O'CLOCK
POSITION
INSTALL BAFFLE AS
REQUIRED IN LAST
SECTION OF TUBE
NOTE:
CLOSE ALL OPEN ENDED "S" HOOKS, CHAIN LINKS,
AND TURNBUCKLES OR ANY OPEN CONNECTION.