Page 13
Modulating Unitary Range
VA-LT206_11292016al
INSTALLATION
Figure 9: Installation of First Section of Flanged Tube
Figure 10: Installation of Heat Exchanger Tube and Coupling
•
Place the first (flanged, aluminized) tube in the first two hangers (Figure 9). Be sure the flange is toward
the intended burner location. The other end of the tube should have the first coupling already loosely
fitted.
•
Always use all the hangers supplied. As a rule the combustion tube (first tube) utilizes 2 hangers and
thereafter 1 hanger per 10’ section. It is required that the first hanging point be 2” to 8” from the burner
mounting flange, and tube weld seam must face down, refer to Figure 9 for more details.
COUPLING SHOULD BE
LOOSELY FITTED
10'
8' - 9'
10'
LOCATE TUBE AND
REFLECTOR HANGERS
EVERY 10' THEREAFTER.
INSTALL "J" BOLT
AT FIRST HANGER
TUBE
FLANGE
TUBE WELD
SEAM FACING
DOWN
3"-5"
COMBUSTION
TUBE
CLOSE ALL OPEN ENDED
QUICK LINKS, CHAIN LINKS,
AND TURNBUCKLES OR ANY
OPEN CONNECTION.
TUBE & REFLECTOR
HANGERS
10'
COUPLING SHOULD BE
LOOSELY FITTED
HEAT
EXCHANGER
TUBE
TUBE WELD
SEAM FACING
DOWN
CLOSE ALL OPEN ENDED
"S" HOOKS, CHAIN LINKS,
AND TURNBUCKLES OR ANY
OPEN CONNECTION.
•
For all remaining tubes, fit the end of the tube with a coupling. The coupling should be loose (Figure 10).
Tube Installation