Installation
61287802F1-34B
37
Revision B
To install the uninterruptible power supply (UPS) complete the following steps:
1. Select a location for the UPS. When making this determination, consider the following:
■ This unit is not appropriate for outdoor placement.
■ Place the UPS in a safe area, free of excessive dust, and with adequate airflow.
■ Refer to UPS technical specifications table for details on temperature and humidity
requirements. Do not operate outside these specified limits.
2. Use the template enclosed with the unit to mark the installation location.
3. Remove the battery cover from the UPS unit and remove the strap from the battery
holding it to the shelf of the unit.
4. Disconnect the battery cable at the battery terminals if already connected to the battery.
5. Remove the battery.
6. Mount the UPS using screws appropriate for the total weight of the UPS and the
mounting surface material.
7. Connect the UPS cable wires (see
).
8. Replace the battery and secure the battery with the strap.
NOTE
g
Refer to the sticker on the bottom of the Power/Alarm Connector if needed.
Figure 15. UPS Power Connection
CAUTION!
f
Mis-wiring the UPS can cause damage to the unit. Use caution when connecting the wiring.
Table 8. UPS Pin-Out Connection
PIN
Description
Color
1
Low Battery
Orange
2
Battery Missing
Blue
3
Replace Battery
Brown
4
On Battery
Grey
+12VDC
12V Return
Signal Return
On Battery
Replace Battery
Battery Missing
Low Battery
Pin 1
Pin 7
Pin 7