Safety and Regulatory
16
61287802F1-34B
Revision B
CAUTION!
C
■ This product contains a Class 1 Laser module that complies with 21 CFR 1040.10 and
1040.11 and IEC 60825-1 and -2. For continued compliance with the above standards,
only approved Class 1 laser modules from an ADTRAN approved vendor list located on
the ADTRAN website should be installed in this product. ADTRAN cannot certify system
integrity with other laser modules.
■ The optical installation is intended to be installed by trained service personnel only.
CAUTION!
f
■ This equipment must be connected to a known, reliable earth ground at all times during
installation and service. Refer to the National Electrical Code (NEC) and state/local codes
for details on grounding requirements. A 12 AWG copper ground conductor shall be used
to connect the equipment to earth ground.
■ The GPON 452/454 does not have an internal DC Connection between 12V and frame
ground.
■ The chassis frame ground terminal must be connected to an earth ground to ensure that
the front panel of the this product is properly grounded.
NOTE
g
■ Power supply input and output conductors of equipment which are outside of the building,
are intended to be less that 100 feet (30.4 meters) and have adequate clearance from
power and lightning conductors in accordance with NEC 725 and 800. Final acceptance
of the Listed equipment installation will ultimately be up to the local Authority Having
Jurisdiction (AHJ).
■ The GPON 452/454 is designed to operate with a nominal operating voltage of 12 VDC.
■ The main feed is optical and therefore not classified as any type of port as defined in
Appendix B of GR-1089-CORE Issue 5.
The GPON 452/454 meets EU RoHS Directive. Refer to
www.adtran.com
for further infor
-
mation on RoHS/WEEE.