L860 Elevated Low-Intensity Edge Light
©
2008 Siemens Airfield Solutions
96A0388B
Page
3-3
All rights reserved
Issued 6/08
7.
There are three power wires present at the bottom of the fixture:
Brown (Line), Blue (Neutral) and Green (Earth Ground). Place the
assembled base plate/fixture close to the base can.
8.
Bring the field circuit (from the previous base can and from the
next base can) into the base can and make a waterproof splice
onto the fixture leads. Refer to Table 2-4.
9.
After you have connected all fixtures, check the continuity of
each of the 3 parallel circuit wires. Also meg each parallel circuit
wire with respect to each other and with respect to earth ground.
10.
Bolt the base plate with the base plate gasket to the L-867 base
using six 3/8
−
16 stainless steel bolts. Apply a drop of Loctite
number 243 to each bolt thread, and use a torque wrench to
torque bolts down to 100/110 inch-pounds (11.3 Nt-m).
Level the light fixture only after mounting it on the light base.
To level the light fixture, perform the following procedure:
1.
See Figure 7-2. Remove Glassware Assembly. Slightly loosen the
three hex screws at the bottom of the housing.
2.
Place a level on top of the housing and rotate housing until level.
Tighten the three hex screws to lock in place.
Light Base Mounting
(cont’d)
Light Fixture Leveling