Wall-Mount, Interior View
Locate each ACE2 unit as close as possible to the controllable elements, the Regulator, the
Generator etc. Mount the CVM and the IRM board (if present) separately from the ACE2.
Mount the Wall-mount ACE2 flush against a wall or on U-channels that support all four
corners of the enclosure.
2.3.2.1 ACE2 Cabling Entry
NOTE:
The ACE2 enclosure is designed to be replaced easily without having to remove the
mounting hardware. Follow these instructions:
1. Position the enclosure flush on its mounting surface. Level the enclosure and open the
lid. Mark or transfer punch the location of the 3/8” diameter holes in each corner of the
enclosure shown in Figure 15.
2. Remove the ACE2 unit and drill the marked holes. Insert anchor hardware as required.
DO NOT DRILL THOUGH THE BOX. Drilling chips and debris can not fall into the
enclosure.
3.
Carefully open the lid of the enclosure. Use ¼-20 x 1.0-inch long screws, flat
washers, and lock washers to fasten the enclosure to the wall or to rails.
4. Mount the enclosure using the top two holes then install the hardware for the bottom two
holes.
5. Attach all conduits to the bottom or to the top access plate ONLY.
6. Protect all equipment inside the ACE2 enclosure while installing conduit.
NOTE:
All conduit and wiring must only enter the ACE2 enclosure through the bottom or the
top access plate. This facilitates quick maintenance and replacement of the ACE2 unit.
There are four knockouts in both the top and bottom of the enclosure walls for one inch EMT
metal conduit fittings for wires and fiber optic cables, see Figures 13 Wall-Mount Bottom View
and Figure 14 Wall-Mount Top View for dimensions. and the Conduit Drawing, Figure 15, for
routing. Power and ACE-to-ACE communication wiring must be in separate conduits.
Attach all conduits as required to the bottom or to the top access plate ONLY as seen in
Figure 15.