44
GB
• When using SMS StartTime and StopTime comprise four-digit num-
bers (HourHourMinuteMinute) and follow a 24-hour clock, e.g. 1900.
• StartTime and StopTime must be within the same day and StopTime
later StartTime.
• Several repeated actions may not be set to run at the same time. The
last repeated action to be set will always be the active one.
Temperature regulation:
• If ADAX SET is connected to a heater and you set the temperature
regulation to 19°C (#159#19# by SMS), ADAX SET will switch ON
when the temperature sinks below 19°C and OFF when it exceeds
19°C. In this way an even room temperature will be maintained.
• Temperatures are in Centigrade. Minimum temperature is –10°C,
maximum temperature is 50°C. In SMS commands temperature is
given with one or two digits, e.g. 23. (Minus temperature is given
with - before the digits.)
• If ADAX SET is to control a heater it is recommended the heater’s
thermostat is set to maximum, or to a temperature higher than that
ADAX SET is programmed for.
•
NB!
Automatic temperature regulation will not control the tempera-
ture during periods when “repeated actions” or “countdown” com-
mand that ADAX SET be turned OFF.
• If temperature regulation is to function, the temperature sensor must
be plugged into the sensor port (2).