PRESTIGE 42-50-75-100-120 Solo : A1007856 - 664Y6200 • G
EN
FR
NL
ES
IT
DE
PL
RU
en
9
USER’S GUIDE
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
CH1 Setpoint
82°C
20°C
87°C
CH2 Setpoint
60°C
20°C
87°C
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
EZ Setup
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
Select CH Demand
Thermostat & Setpoint
Constant & Setpoint
0 - 10 V Modulation Signal
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
Heating EZ Setup
0 - 10V Modulation Signal
- This option allows the Prestige firing rate to be controlled by an external control system.
Refer to the Installer’s Handbook , Volume 1 OR the ACVMax System Control manual for more information (see page 3 for details).
CH1 Setpoint
prompts to enter the fixed setpoint for a CH1 heating call when
a Setpoint option is chosen in Select CH Demand. Press on
LEFT
or
RIGHT
button to adjust the required temperature setpoint then press
OK
to store
the setting. The
CH2 Setpoint
screen appears.
CH2 Setpoint
prompts to enter the fixed setpoint for a CH2 heating call when
a Setpoint option is chosen in Select CH Demand. Press on
LEFT
or
RIGHT
button to adjust the required temperature setpoint then press
OK
to store
the setting and complete the Heating setting.
CH1 Default: 82°C
.
CH2 Default: 60°C
Select CH Demand
prompts the installer to select how a CH Demand is generated. There are three Select CH Demand op-
tions, among which the installer must make a selection.
Thermostat & Setpoint
- This option is only displayed when no outdoor temperature sensor is connected. A central heating call
from a thermostat or zone panel will enable the Prestige and the setpoint will be fixed for central heating calls. When Thermostat
& Setpoint is selected, the CH1 Setpoint screen appears.
Constant & Setpoint
- The Prestige will maintain setpoint without an external CH call from a thermostat or zone panel. The set-
point will be fixed for CH calls. When Constant & Setpoint is selected, the CH1 Setpoint screen appears.
Heating Easy setup (no outdoor sensor connected)
•
To navigate on the screen, use the UP, DOWN, LEFT and RIGHT keys,
OK
•
Use the OK key to validate a selection.
•
To increase/decrease values, use the UP and DOWN keys, or
LEFT
and
RIGHT
, according to the situation