Low Water
Water level has fallen below an
acceptable operating level.
Increase pressure to normal range.
If problem persists,
call for service
E37
Lockout reference code
. Refer to “In case of
Problem...” on page 8 for more information.
Body text.
The first sentence describes the lock-
out, the second sentence gives a possible cure,
and the third tells how to reset the lockout.
Lockout message
. Refer to “In case of Prob-
lem...” on page 8 for more information.
Stand-by
84°C
61°C
Target = --
PRESTIGE 42-50-75-100-120 Solo : A1007856 - 664Y6200 • G
EN
FR
NL
ES
IT
DE
PL
RU
en
7
USER’S GUIDE
LOCKOUT SCREEN
If a problem occurs, the Lockout screen replaces the Home screen. The backlight also remains on as
long as the problem is not solved. Pressing any arrow button will return to the Home screen.
Using the code located in the right bottom corner of the screen, troubleshoot the problem, either
with the table located in paragraph “In case of Problem...” on page 8, or with the Lockout code,
refer to “Locking codes” on page 45.
STAND-BY SCREEN
This screen is displayed at start-up. It indicates that the Prestige is ready to respond when a demand
is received.
STATUS MESSAGES
Stand-by
Indicates that the Prestige is ready to respond when a demand is received.
CH Demand
A central heating call has been received.
DHW Demand
A domestic hot water call has been received.
CH / DHW Demand
Central heating and domestic hot water calls are being received simultane-
ously. Both calls are being satisfied simultaneously because domestic hot
water priority has been disabled.
DHW Priority
Central heating and domestic hot water calls are being received simultane-
ously. Domestic hot water call is being satisfied first because it has priority
over central heating calls.
Priority Timeout
Central heating and domestic hot water calls are being received simultane-
ously. The domestic hot water priority time limit has been exceeded. Priority
will now switch back and forth between central heating and domestic hot
water calls until one call is satisfied.
External Demand
An external modulation call has been received.
Slave Operation
The Prestige is a slave in a cascade system.
Manual Operation
The burner or circulators have manually been enabled in the Installer Menu.
CH Burner Delay
The burner will not fire until the call blocking time has elapsed.
DHW Burner Delay
The burner will not fire until the call blocking time has elapsed.
CH Setpoint Reached
The burner is not fired because the supply/system water temperature ex-
ceeds the setpoint. The central heating circulator continues to operate and
the burner will fire again once the supply/system water temperature drops
below the setpoint.
DHW Setpoint Reached
The burner is not fired because the supply/system water temperature ex-
ceeds the setpoint. The domestic circulator continues to operate and the
burner will fire again once the supply/system water temperature drops be-
low the setpoint.
CH Post Pump
The central heating circulator is running to remove heat from the Prestige at
the completion of a call.
DHW Post Pump
The domestic hot water circulator is running to remove heat from the Pres-
tige at the completion of a call.
Freeze Protection
The burner is fired because the freeze protection feature has been activat-
ed. Freeze protection will end once the supply/system water temperature is
raised to16°C.
Boiler Protection
The burner firing rate is being reduced because of an excessive difference
between the boiler supply and return temperatures. The firing rate will be-
gin increasing once the temperature difference is less than 25°C.
Lockout Description
The lockout which currently has the Prestige shut down is displayed