In case of complex systems, the setup must be performed by an approved installer using the Installer’s Handbook or the
ACVMax System Control manual, according to the software build (refer to page 3 for more information).
Boiler Protection
P3
DHW
P4
84°C
61°C
1
2
CH
Target = 85°C
EZ Setup
Heating EZ Setup
DHW EZ Setup
EZ Setup Reset
Display EZ Setup
PRESTIGE 42-50-75-100-120 Solo : A1007856 - 664Y6200 • G
en
8
EN
FR
NL
ES
IT
DE
PL
RU
USER’S GUIDE
BOILER SETUP GUIDE
The main parameters of the Prestige boilers can be set up using the EZ (easy) setup function of the
ACVMax controller. The EZ setup function allows the user/installer to quickly setup the appliance for
immediate operation according to the system configuration*.
General remarks
•
To navigate on the screen, use the
UP
,
DOWN
,
LEFT
and
RIGHT
keys, then the
OK
key to validate a selection. A selection is marked by a black background under the
selected icon/text.
•
To increase/decrease values, use the
UP
and
DOWN
keys or the LEFT and RIGHT
keys according to the situation.
WHAT TO CHECK ON A REGULAR BASIS
Essential recommendations for the correct operation of the appliance
ACV recommends to check the system at least every 6 months as follows:
•
Check that the system water pressure is at least 1 bar when cold. If the pressure drops
below 0.7 bar, the built-in pressure sensor blocks the appliance until the pressure
exceeds 1.2 bar.
•
If it is required to top up the system to maintain the minimum recommended water
pressure, always turn the appliance off and only add small amounts of water at a time.
If a large amount of cold water is added in a hot boiler, the boiler can be damaged
definitively.
•
If the system needs to be refilled repeatedly with water, please contact your installer.
•
Check that there is no water on the floor under the boiler. If there is, please call your installer.
•
If a condensate neutralisation system is installed, check it and have it cleaned
regularly.
•
Check regularly that there is no error message (lockout) on the screen. A typical
lockout screen is explained on the previous page. Refer also to the Troubleshooting
table below or call your installer as required.
IN CASE OF PROBLEM...
Check the list of faults and corresponding codes below for the solution(s). If no solution is provided, please
contact your installer who will determine the correct solution by referring to”Locking codes” on page 45.
Fault
code
Problem
Possible Cause(s)
Solution
-
The appliance does
not turn on when
pressing the ON/OFF
Master switch
No power supply
Check the power supply and that
the appliance power plug is con-
nected to the network.
E 01
Failed ignition
The burner failed to light
after 5 ignition attempts
Check gas supply to the boiler.
E 13
Reset limit reached
Resets are limited to 5
every 15 minutes
Turn unit OFF and ON to resume
normal operation.
E 34
Low voltage
Line voltage has fallen be-
low an acceptable operat-
ing level
The boiler will automatically reset
once line voltage returns to nor-
mal.
E 37
Low Water
Water pressure has fallen
below an acceptable oper-
ating level (0.7 bar)
Refill the system to reach a nor-
mal range pressure. The boiler
will automatically reset once wa-
ter pressure returns to normal.
E 94
Internal Display Fault
Display memory error
Turn appliance off and on to re-
sume normal operation.