USER’S GUIDE
Select CH Demand
Thermostat & Outd. Curve
Constant & Outdoor Curve
Constant & Setpoint
0 - 10 V Modulation Signal
Select CH Demand
Thermostat & Outd. Curve
Constant & Outdoor Curve
Constant & Setpoint
0 - 10 V Modulation Signal
82°C
27°C
18°C
-12°C
Current Settings
Select CH1 Outd. Curve
MAX
60°C
27°C
18°C
-12°C
Current Settings
Select CH2 Outd. Curve
Warm Weather Shutdown
Off
Off
25°C
EZ Setup Complete
Heating EZ setup is complete.
Additional changes can be made in
the Installer Menu if required.
Press OK to return to EZ Setup Menu
EZ Setup
Heating EZ Setup
Heating Easy Setup (outdoor sensor connected)
Select CH Demand
prompts the installer to select how a CH Demand is generated. There are several Select CH Demand
options, among which the installer must make a selection
.
Thermostat & Outd. Curve –
This option is only displayed when the outdoor temperature sensor is connected. A central
heating call from a thermostat or zone panel will enable the boiler and the setpoint will vary with the outdoor temperature for
central heating calls..
Constant & Outdoor Curve -
This option is only displayed when the outdoor temperature sensor is connected. The Prestige
will maintain the setpoint without an external call from a thermostat or zone panel. The setpoint will vary with the outdoor
temperature for central heating calls.
Select CH1 Outd. Curve
prompts to select an outdoor curve for a CH1 heating call when an Outdoor Reset option is chosen in
Select CH Demand. Outdoor curve presets are available to cover most applications. The outdoor curve can also be adjusted
to any desired settings in the Installer Menu (refer to Installer’s Handbook/System Control Manual, see page 3).
Press on
UP
or
DOWN
button to select the outdoor reset curve appropriate for the type of heating system, then press
OK
to
store the setting.
Default: Systems with a temperature between 27°C and 82 °C
.
Select CH2 Outd. Curve
prompts to select an outdoor curve for a CH2 heating call when an Outdoor Reset option is chosen in
Select CH Demand. Outdoor curve presets are available to cover most applications. The outdoor curve can also be adjusted
to any desired settings in the Installer Menu (refer to Installer’s Handbook/System Control Manual, see page 3).
Press on
UP
or
DOWN
button to select the outdoor reset curve appropriate for the type of heating system, then press
OK
to
store the setting.
Default: Systems with a temperature between 27°C and 60 °C
Warm Weather Shutdown
allows to enter an optional outdoor temperature at which to disable the central
heating function. The Prestige will continue to respond to a domestic hot water call or a 0- 10V Modula-
tion Signal when the outdoor temperature exceeds the Warm Weather Shutdown Temperature setting.
Press the
LEFT
or
RIGHT
buttons to adjust the Warm Weather Shutdown Temperature then press the
OK
button to store the setting and complete the Heating setting.
The Warm Weather Shutdown icon ( ) is displayed on the home screen when the outdoor tempera-
ture reaches the Warm Weather Shutdown preset temperature.
Default: OFF
.