Operations
SDR2-CF/SDR2-OEM-CF Configuration Guide rev 1.0
26
To change the configuration port baud rate, open the enclosure and use
switches S1-1, S1-2 and S1-3 to select a baud rate for the configuration port
and switch S1-4 to enable or disable RTS/CTS hardware handshaking. See
Table
3.1 for switch settings.
Label
baud rate 0
baud rate 1
baud rate 2
RTS/CTS
handshake
enable
Switch
Designator
S1-1 S1-2 S1-3 S1-4
RTS/CTS hardware
handshaking enable
- - -
ON
2400 bps
OFF OFF OFF -
4800 bps
ON OFF OFF -
9600 bps
OFF ON OFF -
19200 bps
ON ON OFF -
38400 bps
OFF OFF ON -
57600 bps
ON OFF ON -
115200 bps
OFF ON ON -
230400 bps
ON ON ON -
Table
3.1. Configuration Port DIP switch settings.
3.3 Lithium battery maintenance
The SDR2-CF's real-time clock uses a small lithium battery to maintain time
when external power is unavailable. The life of this battery should exceed 5
years.
If you find your SDR2-CF is not keeping time correctly or that the time is
displayed with a question mark (
?
) after it when you power up, you may
need to replace the battery. If necessary, replace the battery with a
Panasonic CR2032, or equivalent, making sure the positive (+) face is in
contact with the battery clip. After replacing the battery be sure to reset the
SDR2-CF’s time and date.