INSTALLATION GUIDE

29

Maintenance (cont.)

CHIMNEY CLEANING INTERVALS
It is extremely important to keep the chimney flue clean from products of combustion and deposits. 

Unburned oil residues can cause a chimney fires.

Cleaning intervals depend on the use of the appliance. The more the appliance is used, the more often the 

chimney flue needs cleaning. As there are no firm guidelines for cleaning intervals, have the chimney inspected 

on a regular basis (every quarter or so) to determine what the interval should be. Then follow this interval.
No matter how much used, a chimney flue should be 

cleaned and inspected at least once every year.

NOTE: 

The chimney should be cleaned by a trained professional. We recommend using a “Certifed Chimney 

Sweep” certified by Chimney Safety Institute of American. You can find a Certified Chimney Sweep at www.csia.

org or www.ncsg.org or by calling 

(317) 837-5362 or (317) 837-1500.

OBSERVATION

PROBLEM

SOLUTION

There is no power going to the fan

- The circuit breaker may be off

- Fan speed control is off

- Bad electrical connections

- Check the circuit breaker

- Turn fan speed control

- Check and correct problem

There is power to the fan but it is 

not operating

- Bad electrical connections

- The fan speed control’s low 

   voltage setting is too low

- The fan speed control is bad

- Check and correct problems with 

  connections. Pay special attention 

  to the wiring in the junction box

- Increase the setting with the 
  plastic screw on the fan speed 

  control’s front plate

- Replace the fan speed control

There is power to the fan but it 

hums and does not turn

- The motor run capacitor may 

   be bad.
- Creosote may stick

- Check capacitor and replace 

  if necessary

- Clean fan

There is airflow noise from the draft 

hood

- The fan is oversized and running   
   too fast

 - Reduce the fan speed

Mechanical noise can be heard

- Foreign matter may be stuck
- Motor bearings may be worn out

- Remove foreign matters
- Replace bearings

Troubleshooting

Chimney Fan

BL_ST_INSTL_RevB_4.08.19

Содержание Blaze BL-6-ST

Страница 1: ...cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure...

Страница 2: ...sure cap 4 CERTIFIED FOR UNITED STATES Lab Test ANSI Z21 50 2016 DO NOT REMOVE THIS LABEL MANUFACTURER Serial 90039 Acucraft Fireplaces VENTED GAS FIREPLACE MODEL BL 8 ST 19672 172nd St Big Lake MN 55...

Страница 3: ...nstalling the Ventilation System pg 17 19 Installing the Media pg 20 Installing the Glass Panel pg 21 Components Gas Valve Ignition Module pg 22 Draft Switch pg 23 24 Chimney Fan pg 25 29 Component Qu...

Страница 4: ...evolutionize the fireplace industry not by being the biggest but by being the best We push ourselves to do more than we think we are capable of We are a family first organiza tion and we strive to be...

Страница 5: ...rm present Caution statements will occur when there presents a risk of damage to the unit if the statements are not followed correctly Below are examples of what the statements look like This statemen...

Страница 6: ...lace will become hot while in use Hot glass will cause burns Keep children away from hot surface to avoid burns or clothing ignition Never touch glass until cooled If burns occur seek immediate medica...

Страница 7: ...fully supervised when they are in the same room as the appli ance Toddlers young children and others may be susceptible to accidental contact burns A physical barrier is recommended if there are at ri...

Страница 8: ...e must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of psi 3 5 k Pa The appliance must be isolated from the gas valve supply...

Страница 9: ...9 COMPONENT ILLUSTRATION BLAZE 6 8 ST STT INSTALLATION GUIDE BL_ST_INSTL_RevB_4 08 19...

Страница 10: ...30 1 2 3 CONFIG SW 2 HW RST SW RST PG TIME FAN SPD SW 1 SW 3 L1 NEUT GND L1 NO NC GND COM NO SIG GND COM NO 0 10 GND 24V 0 10 GND NEUT GND COM NO COM NO RELAY PROVE RELAY CONTROL L1 NEUT GND Acucraft...

Страница 11: ...The appliance is designed to sit either directly on the floor or to sit on a base designed to support the weight of the appliance for proper elevation If shimming is required to level the appliance d...

Страница 12: ...s Class A exhaust flue 2 IMPORTANT Clearances must be in accordance with local installation codes and the requirements of the gas supplier FRAMING DIMENSIONS Measured from the bottom of the unit MODEL...

Страница 13: ...into the framing around the unit as shown above The backer board may be fastened to the unit with fasteners that do not penetrate the fireplace more than 1 There should NOT be any fasteners in the 3 b...

Страница 14: ...14 INSTALLATION GUIDE The shaded area in the drawing above is the non combustible zone All finishing material in this area is to only be non combustible BL_ST_INSTL_RevB_4 08 19...

Страница 15: ...nimum clearance of 12 from the top of the frame to the bottom of the mantel Steel stud framing and non com bustible finish does not require a clearance Note there should be a 1 8 clearance from the fr...

Страница 16: ...16 INSTALLATION GUIDE Distance to any side adjacent wall must be at least 12 inches from the outside of the glass frame BL_ST_INSTL_RevB_4 08 19...

Страница 17: ...nting configuration may or may not include any or all of the following components depending on design proven draft switch model PDS 1 or ventilation fans Exhaust Flue When installing the UL103HT Class...

Страница 18: ...appliances 10 000 Btuh 3 kW 12 in 30 cm for appli ances 10 000 Btuh 3 kW and 100 000 Btuh 30 kW 36 in 91 cm for appliances 100 000 Btuh 30 kW 6 in 15 cm for appliances 10 000 Btuh 3 kW 9 in 23 cm for...

Страница 19: ...uilt duct ing Further installation instructions can be found at www icc rsf com These units are approved to use UL103HT ducting Note If ducting is not purchased from Acucraft no Flue anchor plate will...

Страница 20: ...The media trays on either side should be filled with the desired media glass stones etc This fireplace burner requires a layer of media to cover the burner tube allowing proper dispersion of the gas...

Страница 21: ...er Glass Panel into track as shown Place middle frame assembly into opening push tight up to permanent glass frame Place bolts in spaces provided to attach middle frame assembly to firebox Place outer...

Страница 22: ...and installed by qualified persons only and checked and tested for leaks prior to wiring of valve module Gas supply should be connected as shown below Shut off supplied by other Directions for Connec...

Страница 23: ...n with the pressure connection pointing down Secure the switch by using the mounting holes as shown After installation connect the tubing from the probe onto the port marked accessible through the sma...

Страница 24: ...ine screws Tighten the end cap to compress the ferrule and permanently install the stack probe Attach the supplied silicon tubing at the other end of the probe Draft Switch STACK PROBE ALTERNATE LOCAT...

Страница 25: ...pacities C A D B E 1 12 11 10 9 8 7 6 5 4 3 2 1 Junction Box 2 Conduit Cord 3 Motor 4 Motor Housing 5 Cooling Plates 6 Bird Screen 7 Base Plate 8 Locking Nut 9 Inlet 10 Axial Vane 11 Hinges 12 Capacit...

Страница 26: ...the chimney fan must be secured by steel wires supplied with the fan CAUTION Step 1 Prepare fan location The steel chimney adapter SCA slides right into the chimney where the long collar engagement en...

Страница 27: ...requirements of the authority having jurisdiction or in the absence of such requirements with the National Electrical Code NFPA 70 latest edition Termination of Venting System In order to achieve opt...

Страница 28: ...an ON and make sure that it is operating Increase and decrease the speed of the fan by adjusting the fan speed control to make sure it is operating properly 2 Turn the fan OFF and make sure the pressu...

Страница 29: ...837 5362 or 317 837 1500 OBSERVATION PROBLEM SOLUTION There is no power going to the fan The circuit breaker may be off Fan speed control is off Bad electrical connections Check the circuit breaker T...

Страница 30: ...ng Acucraft Service by phone or email Acucraft Customer Service Contact Information Phone 763 263 3156 Email service acucraft com WARNING Failure to position the parts in accordance with this manual o...

Страница 31: ...42 24 27 BL 6 STT 72 75 84 57 22 11 7 1 2 11 21 42 30 33 BL 8 ST 96 99 108 53 24 12 8 12 30 54 24 27 BL 8 STT 96 99 108 59 24 12 8 12 30 54 30 33 BLAZE 6 8 ST STT A B 4 1 2 11 K L D 12 1 2 2 4 C 2 G F...

Страница 32: ...d 2 Remove control access panel 3 Push in control knob slightly and turn clockwise 4 Replace control access panel 1 STOP Read the safety information above on this label 2 Turn off all electric power t...

Страница 33: ...The fireplace control switch is turned on 2 Control Board proves and engages fan 3 Pressure switch sends signal to control board proving draft 4 Control board closes AUX output energizing igni tion c...

Страница 34: ...still sparking with no ignition contact a qualified technician The appliance ignites but shuts down shortly after ignition The flame sensor may not be registering proper flame strength Turn the appli...

Страница 35: ...is connected it begins to open Once open the damper prove contact closes Terminals 16 and 17 3 The ADC100 begins to ramp up the fan 4 The Proven Draft Switch closes when adequate draft is achieved and...

Страница 36: ...appliance service valve 2 Paint pipe connections upstream of pilot burner with rich soap and water solution Bubbles indicate gas leak 3 If leak is detected tighten pipe connections 4 Stand clear of m...

Страница 37: ...ICE TOO SMALL PILOT OUTAGE 1 If pilot flame goes out during normal operation but is properly adjusted recheck Mounting and Location instructions 2 If all mounting and location instructions are followe...

Страница 38: ...d annually by a qualified service technician Examination and visual check of the burner flame should be performed periodically to ensure proper operation If the flame deviates greatly from the standar...

Страница 39: ...Acucraft gas appliance must be subjected to normal use The gas appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damag...

Страница 40: ...Acucraft Fireplaces 19672 172nd Street Big Lake MN 55309 FIRE IS OUR PASSION www acucraft com 888 317 6499 BL_ST_INSTL_RevB_4 08 19...

Отзывы: