4
Control Installation
approx. 1.5m
from the ground
Location
•
ENSURE that the wall controller is installed in a location that is within the range of
applicable WiFi access point. The distance is dependent on router model and brand.
Refer to your unit access point manual.
•
ENSURE that the wall controller is installed in a location that is within the
recommended range of RF signal of all connected zone devices. Maximum range is
30 metres line of sight and unobstructed.
•
Do not install the wall controller on external walls, directly below the supply air grille
or near other additional heat load sources, as these locations may alter
sensor readings.
•
Do not install the master controller near magnetic, metallic objects or install near
power cables as these may effect the wireless data signal it sends and receive.
•
Avoid looping excess cable.
•
Ensure there is ample space around the wall controller (100mm min) to ensure
proper air temperature reading and adequate access for service.
•
It is required to use the provided wall anchors and screws to secure device on
the wall.
•
DO NOT swap the master controller and secondary wall controller after setup.
•
Use the included 10m yellow Cat5E spec cables with RJ45 connectors & cable boot.
For longer cable requirements upto 30m in length, an optional 20m cable and RJ45
connector are available separately.
•
Use only the allocated indoor board terminal to connect the controllers.