Installation and Commissioning Guide
Hercules Package Unit
27
Installation and Commissioning Guide - Hercules Package Unit
Doc. No.0525-021
Ver. 21 221110
Circuit Breaker Requirement
Circuit Breaker Size
Model
Circuit Breaker Size (Amps)
PKV1400T
100
PKV2000T
125
Compressor Voltage Balance Requirement
Check the voltage at the compressor terminals to determine if it is balanced. Voltage imbalance on three phase systems can
cause motor overheating and premature failure. The maximum allowable imbalance is + 2.0%, check unit wiring connections
to locate and rectify faults, should voltage imbalance exceed this value.
13. Maximum Cable Lengths
4 CORE (2-PAIR) TWISTED
PAIR
2/0.5mm2 (AWG24)
SHIELDED DATA CABLE
(Installer to Provide)
4
(OPTIONAL DUAL CONTROL)
CONTROL INTERFACE
ActronAir CP05 / CP10
(Purchased Separately)
(OPTIONAL REMOTE RE-LOCATION)
CONTROL INTERFACE **
ActronAir CP10
(Factory Supplied)
CP05 - or - CP10
2
6
5
3
2
Esc
Prg
3RD PARTY CONTROL
INPUT TERMINALS
7
1
NTC SENSOR CABLE
(Factory Supplied)
6 CORE (3-PAIR)
TWISTED PAIR
7/0.20 (AWG24)
SHIELDED DATA
CABLE
(Installer to Provide)
or
6 CORE FLAT
7/0.12 (AWG28)
TELEPHONE CABLE
(Installer to Provide)
OP
E
N
CL
O
S
E
OP
E
N
CL
O
S
E
(OPTIONAL CRH-D)
OUTSIDE HUMIDITY SENSOR
(Purchased Separately)
(OPTIONAL CRH-S)
ROOM HUMIDITY SENSOR
(Purchased Separately)
Esc
Prg
NTC SENSOR CABLE
(Factory Supplied)
- or -
ActronAir LM-RS
(Optional)
ActronAir 2060-030 *
(Factory Supplied)
ROOM AIR TEMPERATURE SENSORS