Installation and Commissioning Guide
Variable Capacity Commercial
9
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Outdoor Unit
Doc. No.0525-066 Ver. 6 221012
06. Outdoor Unit Dimensions and Clearances
06.01. Unit Dimensions and Weights
CRV290T / CRV330T
OVERALL NOMINAL DIMENSION (H x W x L)
= 1415 x 1840 x 820
MOUNTING DRAIN CONNECTION =
DN 25mm PN12
NOTES:
1. Do not scale drawing. All dimensions
are in mm unless specified. Refer to
corresponding unit dimensional drawing for mounting
hole details.
2. Service Access Areas and Spaces for Airflow Clearances
given above are suggested minimum based on the
condition that the spaces around the units are free from
any obstructions and a walkway passage of 1000mm
between the units or between the unit and the outside
perimeter is available.
3. Minimum service access areas and spaces for airflow
clearances are responsibilities of the installer, ActronAir
will not be held liable for any extra charges incurred due
to lack of access and space for airflow.
4. Under all circumstances, condenser air must not
recirculate back onto condenser coil. Keep all clearance
free of any obstructions.
5. STACKING OF UNITS: Ensure that minimum airflow and
clearances are met.
6. Refer to Pipe Connection Details on Specifications Sheet.
7. MTG C-C DIST = Mounting Centre to Centre Distance.
8. Use M12 bolt for feet mounting.
THIRD ANGLE
PROJECTION
DRAIN POINT
DN 25mm PN12
ELECT. ACCESS
2 x Ø 25.4 mm (1")
GAS PIPE
Ø 28.6 mm (1-1/8")
SWAGED
LIQUID PIPE
Ø 15.88mm (5/8")
SWAGED
1179
106
35
750 (MTG C-C DIST)
35
408
660
1840 0/A
392
87
820 O/A
1415 O/A
60
757
150
1540 (MTG C-C DIST)
150
OUTDOOR COIL
COMP
TOP VIEW
FRONT VIEW
SIDE VIEW