Installation and Commissioning Guide
Variable Capacity Commercial
37
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Outdoor Unit
Doc. No.0525-066 Ver. 6 221012
4. Press the
or
buttons to select OFF. Then press the
PROG
button to accept.
5. Press the
BACK
button twice to go back to the original status display.
NOTE
Setting up “Fan Continuous ON/OFF” is only available through LC7-2 Control.
14.04.0�. Compressor Soft Start Option
If an ActronAir compressor soft starter (sold separately) will be installed, it is necessary to enable this in OD Board
Menu. However, if the soft starter is already pre-installed with the unit (“-Z Option”), no set up is necessary.
Procedure:
1. Using the
MENU
and the
ENTER
buttons, navigate to
SEt
(Settings)
SoFt
(Soft Start Settings).
2. If required, press
MENU
to navigate to
YES
. By default, this is set to
no
.
14.04.09. Run and Fault Indication Output
Run Output is confi gurable to indicate that the unit is running. There are two confi gurations in which this can be set
●
Either the compressor or the Indoor Fan only is running
●
Only Compressor is running.
By default, this is set to
no
, where indicator will turn on when either on ID Fan Only Operation mode or Compressor
is running. To set up to compressor run indication only, in OD Board Menu follow below steps.
Procedure:
1. Using the
MENU
and the
ENTER
buttons, navigate to
SEt
(Settings)
run
(Unit Operation Indicator Settings).
2. If required, press
MENU
to navigate to
YES
.
15. Optional Output/Input Relay
15.01. Filter Indication Relay Output (Indoor Board)
Allows for optional connection for Filter Indication Relay (10A/240V). Option to use either normally open or normally
close relay.
NOTE
To reset the alarm notifi cation via Outdoor Board (no LC7-2 connected) , set the time again to clear/reset the fi lter alarm
output.