Installation and Commissioning Guide
Variable Capacity Commercial
23
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Outdoor Unit
Doc. No.0525-066 Ver. 6 221012
12.02. Wiring Configuration : Recommended
Item
Description
Maximum Cable Length
1 to 4
Outdoor PCB to Indoor PCB
100 m
4 to 2a, 4 to 2b,
Indoor PCB to Wall Controller
90 m
4 to 2C
Indoor PCB to Wall Controller
100 m
4 to 3
Indoor PCB to Remote Sensor
100 m
Description
Cable Type
LC7-2 and NEO Field Control Wiring
Cat5E UTP (AWG 24) Data Cable
Indoor to Remote Sensor
Cat5E UTP (AWG 24) Data Cable
Indoor to Outdoor Data Cable
2 Core (1 Pair) Twisted Pair, 7/0.30 (0.5mm
2
) Shielded Data Cable
5
NEO SENSE
(OPTIONAL)
4
INDOOR UNIT
DATA CONTROL
CABLE
3
LM-RS
-2
(OPTIONAL)
AERSS
(OPTIONAL)
2a
NEO
WALL CONTROLLER
1
(OPTIONAL)
2b
NEO
WALL CONTROLLER
2
(OPTIONAL)
LC7-2
WALL CONTROLLER
3
(OPTIONAL)
2c
1
NOTES
•
Max. of 16 NEO Sense per System.
•
NEO Sense is battery powered.
•
NEO Sense is available in White (NSW-10)
and Black (NSB-10).
NOTES
• Diagram shown below is a general representation only. Refer to individual unit wiring diagram for complete wiring
connection details.
• Long runs beside Mains cables or TV antenna cables should be avoided.
• Wiring confi guration for LR7-1 and LC7-2 wall controller is the same.
• Daisy connection is not allowed for the NEO wall controller.
• Two Ferrite Clips*, if supplied, are to be placed 200mm and 400mm from the NEO controller.
* 2 Ferrite Clips
* 2 Ferrite Clips