16
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Outdoor Unit
Doc. No.0525-066 Ver. 6 221012
Installation and Commissioning Guide
Variable Capacity Commercial
CAUTION
Above illustration shown as calculation examples only. It is the responsibility of the Installer to design an effi cient
refrigeration piping lay out for optimum unit performance.
TABLE 2: REFRIGERATION PIPING
Outdoor Model
CRV290T/330T
Indoor Model
EVA290T/330T
Equivalent Pipe Length Range
metres
0 - 60
Maximum Vertical Height Diff erential
*
metres
20
Field Pipe Size
Liquid Line
mm (inch)
15.88 (5/8)
Gas Line
mm (inch)
28.58 (1-1/8)
Outdoor Pipe Size
Liquid Line
mm (inch)
15.88 (5/8) swaged
Gas Line
mm (inch)
28.58 (1-1/8) swaged
Indoor Pipe Size
Liquid Line
mm (inch)
15.88 (5/8) swaged
Gas Line
mm (inch)
28.58 (1-1/8) swaged
*
Included in maximum fi eld pipe
CAUTION
Brazing joints should only be performed whilst purging Nitrogen through the system. Failure to do so will cause carbon
deposits to be left on the internal pipe surface, that in turn can cause system failure and void of warranty.