24
Installation and Commissioning Guide - Split Ducted Variable Capacity Commercial Outdoor Unit
Doc. No.0525-066 Ver. 6 221012
Installation and Commissioning Guide
Variable Capacity Commercial
12.03. Wiring Configuration 2 : Alternate
2a
LC7-2
WALL CONTROL 1
(OPTIONAL)
LC7-2
WALL CONTROL 2
(OPTIONAL)
LC7-2
WALL CONTROL 3
(OPTIONAL)
2b
2c
4
INDOOR UNIT
DATA CONTROL
CABLE
3
LM-RS
-2
(OPTIONAL)
AERSS
(OPTIONAL)
1
NOTES
• Diagram shown above is a general representation only. Refer to individual unit wiring diagram for complete wiring
connection details.
• Long runs beside Mains cables or TV antenna cables should be avoided where possible.
Item
Description
Maximum Cable Length
1 to 4
Outdoor PCB to Indoor PCB
100 m
4 to 2a
Indoor PCB to Wall Control 1
100 m
4 to 2c
Indoor PCB to Wall Control 3 (last controller)
75m total (Daisy Chain)*
4 to 3
Indoor PCB to Remote Sensor
100 m
* Maximum Daisy Chain connection is up to 2 wall Controls.
Description
Cable Type
LC7-2 Field Control Wiring
Cat5E UTP (AWG 24) Data Cable
Indoor to Remote Sensor
Cat5E UTP (AWG 24) Data Cable
Indoor to Outdoor Data Cable
2 Core (1 Pair) Twisted Pair, 7/0.30 (0.5mm2) Shielded Data Cable