5. Setting up the device
Threshold values / limits,
LI-1:
Default:
200.0
This value defines the threshold, that activates/deactivates an alarm.
Setting up the initial value of the analog output,
Out.OF:
Default:
-200,0
The final value is adjusted from the smallest digit to the highest digit with
[
▲
] [
▼
]
and digit by
digit confirmed with
[P]
. A minus sign can only be parameterised on the highest digit. After the
last digit, the device changes back into menu level.
Setting up the final value of the analog output,
Out.En:
Default:
850.0
The final value is adjusted from the smallest digit to the highest digit with
[
▲
] [
▼
]
and digit by
digit confirmed with
[P]
. A minus sign can only be parameterised on the highest digit. After the
last digit, the device changes back into menu level.
Hysteresis for limit values,
HY-1:
Default:
0.0
The delayed reaction of the alarm is the difference to the threshold value, which is defined by
the hysteresis.
Selection of analog output,
Out.rA:
Default:
4-20
Three output signals are available: 0-10 VDC, 0-20 mA and 4-20 mA, with this function, the
demanded signal is selected.
Setting up the display time,
SEC
:
Default:
1.0
The display time is set with
[
▲
] [
▼
]
. The display moves up in increments of 0.1 up to 1 second
and in increments of 1.0 up to 10.0 seconds. Confirm the selection by pressing the
[P]
button.
The display then switches back to the menu level again.
Parameterisation level
Menu level
then