5. Setting up the device
11
Input variable of process value,
SIG.in
:
Default:
a.meas
With this parameter, the device can be controlled via the analog input signals
a.meas
= 0-20 mA,
4-20 mA or 0-10 VDC or via the digital signals of the interface
M.bus
= RS232/RS485 (Modbus
protocol). With
[P]
the selection is confirmed and the device changes into menu level.
Display overflow,
dI.OUE:
Default:
99999
With this function the display overflow (
_ _ _ _ _
) can be defined on a definite value.
Back to menu group level,
rEt:
With
[P]
the selection is confirmed and the device changes into menu group level
„–INP–“
.
Device undercut,
dI.Und:
Default:
-i9999
With this function the device undercut (
_ _ _ _ _
) can be defined on a definite value. Exception is
input type
4-20 mA
, it already shows undercut at a signal <1 mA, so a sensor failure is marked.
Setting up the display time,
SEC
:
Default:
1.0
The display time is set with
[
▲
] [
▼
]
. The display moves up in increments of 0.1 up to 1 second
and in increments of 1.0 up to 10.0 seconds. Confirm the selection by pressing the
[P]
button.
The display then switches back to the menu level again.
Parameterisation level
Menu level
then