ACS-CONTROL-SYSTEM GmbH
l Lauterbachstr. 57 l D-84307 Eggenfelden l www.acs-controlsystem.de l [email protected]
27
25
9. Technical data
9. Technical data
0/4-20 mA / burden
≤
500
Ω
or 0-10 VDC /
≥
10 k
Ω
, 16 bit
Analog output
Output
approx 0.1°C or 0.1°F
Resolution
Accuracy
±1
0.1 % of measuring range
-328.0…1562.0°F
Pt100 3-/4-wire
EPDM, 65 Shore, black
Sealing material
±1
0.1 % of measuring range
-200.0…850.0°C
Pt100 3-/4-wire
U/F-converter
Measuring principle
0.1…10.0 seconds
Measuring time
100 ppm / K
Temperature drift
92.0
+0,8
x 45.0
+0,6
mm
Panel cut-out
96x48x139 mm (BxHxD) incl. plug-in terminal
Digit
Measuring error
Measuring range
Input
0.1 to 10.0 seconds
Display time
horizontal bars at the bottom
Underflow
horizontal bars at the top
Overflow
one LED per setpoint
Setpoints
-19999 to 99999
Range of display
red (optional blue/green/orange)
Segment colour
14 mm
Digit height
Display
plug-in terminal; wire cross section up to 2.5 mm
2
Connection
approx. 300 g
Weight
standard IP65 (Front), IP00 (Back side)
Protection class
PC Polycarbonate, black, UL94V-0
Material
screw elements
Fixing
to 15 mm
Wall thickness
96x48x120 mm (BxHxD)
Dimensions
Housing