IntelliPack Series 841T Transmitter/Alarm User's Manual                                                                Frequency Input 
___________________________________________________________________________________________ 

 - 9 - 

 
Unipolar Signal Configuration: 

Input Amplitude:

  0 to 3V minimum range, 0 to 100VDC 

maximum range. 

Input Threshold:

  Configurable for 1.5V or 5V, typical. 

Input Hysteresis:

  Configurable for 

25mV (at 1.5V 

threshold), or 

83mV (at 5.0V threshold), typical. 

Bipolar Signal Configuration: 

Input Amplitude (0-20KHz):

 

50mV minimum (with 

25mV hysteresis) or 

150mV minimum (with 

83mV 

hysteresis), to 

100V peak-to-peak maximum. 

Input Amplitude (Above 20KHz):

 

100mV minimum 

(with 

25mV hysteresis) or 

200mV minimum (with 

83mV hysteresis), to 

100V peak-to-peak maximum. 

Input Threshold:

  0mV nominal, 0.01V typical with 

25mV hysteresis; 0.03V typical with 

83mV hysteresis. 

Input Hysteresis:

  Configurable for 

25mV or 

83mV, 

typical. 

 
Minimum Input Pulse Width:

  Frequency inputs: 10us 

Pulse counting inputs:  5ms.

 

Input Overvoltage Protection:

  Bipolar Transient Voltage 

Suppressers (TVS). 

Resolution:

  The sampling mechanism used for the 100Hz 

and 1000Hz ranges results in decreased internal resolution 
with increased frequency.  This resolution is generally better 
than the display resolution indicated in Table 4.  However, as 
the input frequency approaches the upper end of the 100Hz & 
1000Hz ranges, the reduced internal resolution effectively 
approaches twice the display resolution noted in Table 4 for 
these ranges. 

 

Table 4:  Input Range Resolution 

Input Range 

Display Resolution 

0 to 100.00Hz 

0.01Hz 

0 to 1000.0Hz 

0.1Hz 

0 to 50000Hz 

1Hz 

0 to 65535 Pulses 

1 Pulse 

 
Input Zero/Span Range Turn-Down (See Table 5):

  The 

configuration software may be used to calibrate an output 
response to input zero & full-scale values that are subsets of 
their nominal input range end points.  For best results, select 
the smallest input range that contains the desired zero and 
full-scale input signals.  Refer to Table 5. 

 

Table 5:  Input Zero/Full-Scale Span Selection 

Nominal 
Input Range 

Recommended Input Span Calibration 
Range 

0 to 100.00Hz 

10Hz min span within 0 to 100Hz range. 

0 to 1000.0Hz 

100Hz min span within 0 to 1KHz range. 

0 to 50000Hz 

1000Hz min span within 0-50KHz range. 

0 to 65535 

Pulses 

1000 pulses min span recommended. All 
spans must include 0 as low endpoint. 

 

Input & Alarm Accuracy: 

 Module timing is crystal based for 

best accuracy, temperature stability, and minimum long term 
drift.  For input and alarm accuracy refer to Table 6.  Table 6 
does not include analog output or overall accuracy (refer to 
Table 7).  Note that the sampling mechanism used for the 
100Hz and 1000Hz ranges results in decreased resolution 
near the upper end of the range, thus decreasing effective 
accuracy in this range.   

 

 
Table 6:  Input Measurement & Alarm Accuracy 

Nominal 
Input Range  

 
Accuracy at 25

Accuracy Over 
Temperature 

0 to 100.00Hz 

0.02Hz (f 

 50Hz) 

0.04Hz (f 

 50Hz) 

0.04Hz (f 

 50Hz) 

0.06Hz (f 

 50Hz) 

0 to 1000.0Hz 

0.2Hz (f 

 500Hz) 

0.4Hz (f 

 500Hz) 

0.4Hz (f 

 500Hz) 

0.6Hz (f 

 500Hz) 

0 to 50000Hz 

+/-10Hz 

+/-15Hz 

0 to 65535 
pulses 

+/-1 pulse 

+/-1 pulse 

 
Input Impedance:

 35K

, typical. 

Input Response Time/ Input Filter Bandwidth:

  -3dB at 35KHz, 

typical.  See also Input Acquisition Time, Relay Response 
Time, and Output Update Rate for more information. 

Input Acquisition Time:

  Frequency inputs:  100mS to 1 second 

(varies with input frequency).  Pulse counting inputs:  Input 
polling every 5ms (samples event at a 1.2ms rate). 

Input Pullup/Pulldown:

  Software selectable 2.7K

 input pullup 

to +5V and a 1K

 input pulldown to return. 

Input Debounce (Pulse counting inputs only):

  0 (disabled) to 

1 second, configurable in 5ms increments.  You must select 
appropriately with respect to input signal bandwidth and 
characteristics. 

Input Averaging (Frequency inputs only):

  Running average of 

1 (disabled by default), 2,4,8, or 16 input samples, software 
configured.  Input averaging > 1 will increase the response 
time. 

Noise Rejection (Normal Mode): 

 Not Applicable. 

Noise Rejection (Common Mode):

  80dB @ 60Hz, typical with 

100

 input unbalance. 

Input Excitation Supply:

  +12VDC or +8.2VDC, typical at 10mA 

load (current limited to approximately 24mA). 

Counter Reset Input:

  TTL or open collector/drain signal (5V 

logic) may be wired directly to the input terminals of the 
module to reset the counter value to 0.  Signal is active low.  
Minimum reset pulse width is 5mS.  Note that the counter can 
also be reset to zero by clicking on the “Reset Event Count” 
button of the IntelliPack Configuration Software. 

Frequency Input Reference Test Conditions:

  0 to 50KHz 

Bipolar 5Vpp input; Threshold 0.0V; Hyst/-25mV; 
Input Averaging = 1; Ambient = 25

C; Power Supply = 

24VDC; Output = 4-20mA, Ascending (4mA represents 0Hz; 
20mA represents 50KHz).  For 841T-1500 units, additionally:  
Relay High Limit at 50KHz; 250Hz Deadband; Automatic 
relay reset; Failsafe mode; Relay Time Delay of 100mS. 

Pulse Counting Input Reference Test Conditions:

  0 to 25K 

pulses; Unipolar 0 to 5V input; Threshold 1.5V; Hyst/-
25mV; Count positive pulses with Automatic Reset; Input 
Debounce = 0; Ambient = 25

C; Power Supply = 24VDC; 

Output = 4-20mA, Ascending (4mA represents 0 pulses; 
20mA represents 25K pulses).  For 841T-1500 units, 
additionally:  Relay High Limit at 25K pulses; Automatic relay 
reset; Failsafe mode; Relay Time Delay of 100mS. 

 
 

ANALOG OUTPUT SPECIFICATIONS 

 

These units contain an optically isolated DAC (Digital-to-

Analog Converter) that provides a process current or voltage 
output.  Calibration can occur with respect to any output range, 
but only one of the outputs may operate at a time. 
 

Содержание IntelliPack 841T

Страница 1: ...Frequency or Pulse Counting Input USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1997 Acromag Inc Printed in the USA D...

Страница 2: ...T are registered trademarks of Microsoft Corp 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter models listed in Table 1 Supplementary sheets are attached for units w...

Страница 3: ...lity of this device to be reprogrammed many times Convenient Field Reprogrammability Adjustment to transmitter zero and full scale plus alarm setpoint and deadband can be made via module push buttons...

Страница 4: ...he common DB9P serial port connector of a host computer The adapter also has a 6 wire RJ11 phone jack to connect to the IntelliPack alarm module via a separate interconnecting cable described below Re...

Страница 5: ...ages from the rail Electrical Connections Terminals can accommodate wire from 12 24 AWG stranded or solid copper Strip back wire insulation 1 4 inch on each lead before installing into the terminal bl...

Страница 6: ...tage meter is required to monitor the output level This meter must be accurate beyond the module specifications for best results Note The module s input frequency range must already be set via the Int...

Страница 7: ...d Configuration LED Program Indication LED INDICATOR Constant ON FLASHING Yellow Zero Full Scale labeled Z FS Zero Full Scale 841T 1500 Only Yellow Relay labeled RLY High or Low Setpoint High or Low D...

Страница 8: ...rking and powered serial interface adapter Acromag s Application Engineers can provide further technical assistance if required When needed complete repair services are available from Acromag 6 0 SPEC...

Страница 9: ...tion near the upper end of the range thus decreasing effective accuracy in this range Table 6 Input Measurement Alarm Accuracy Nominal Input Range Accuracy at 25 C Accuracy Over Temperature 0 to 100 0...

Страница 10: ...tacts The relay operates as a limit alarm with control of deadband hysteresis latching non latching contacts failsafe non failsafe modes plus relay time delay SPDT Alarm Relay Specifications 841T 1500...

Страница 11: ...static Discharge ESD Immunity Complies with IEC1000 4 2 Level 3 8KV 4KV air direct discharge to the enclosure port and European Norm EN50082 1 Surge Immunity Complies with IEC1000 4 5 Level 3 2 0KV an...

Страница 12: ...t Range Unit can be configured for either a voltage or current output range A jumper must also be installed between the output I and JMP terminals for voltage output remove this jumper for current out...

Страница 13: ...m state or non failsafe operation relay energized in alarm state Failsafe mode provides the same contact closure for alarm states as for power loss while non failsafe mode uses alarm contact closure o...

Страница 14: ...SIENT SUPPRESSION DEVICES NOT SHOWN BRTN INP UT 2 3 2 2 FQ IN 5 V INPUT SIGNAL CONDITIONING HYSTERESIS DIV PD BIPO PUP COMPARATOR SERIES 841T SIMPLIFIED SCHEMATIC UNIP REF 1 5 V INPUT ISOL ATION MODE...

Страница 15: ...ency Pulse Counting Counts Counts ANALOG INPUT MODEL 811T 1500 ONLY PV PV Percent SEN SOR INPUT BLOCK RANGE ADJUST BLOCK PV Transfer Function Linear Proportional Configuration Variables High or Low Li...

Страница 16: ...IntelliPack Series 841T Transmitter Alarm User s Manual Frequency Input ___________________________________________________________________________________________ 16...

Страница 17: ...0 T O 3 6 VDC REL AY CO NNECTIO NS Acromag GROUND T B4 M O D E RE L AY P WR 8 4 1 T 1 5 0 0 REMO TE EXTERNAL CO UNTER RESET SW I T CH OPEN COL L ECT OR SEE T B2 INPUT CONNECT IONS ON PAGE 2 PRACT ICES...

Страница 18: ...T NOT E 2 T HIS GROUND CONNECT ION IS RECOMMENDED F OR BEST USE CAUT I ON AND AVOID MAKING ADDIT IONAL GROUND CONNECT IONS W HICH COUL D GENERAT E GROUND L OOPS AND MEASUREMENT ERROR T B2 E X C E X C...

Страница 19: ...21 24 CONTACT FIGURE A 46 TB4 TB3 GROUND CONTACT FIGURE B RELAY 46 43 45 N O COM 35 42 JMP TB3 PWR 32 34 31 DC V DC 11 14 12 TB2 22 15 25 23 26 DIODE DC LOAD TB4 N C MOV AC LOAD TB4 N C SPDT CONTACTS...

Страница 20: ...________________________________ 20 RUN Acromag RLY S T Z FS 118 9 4 68 95 3 3 75 MODE S E T D IN EN 50022 35mm T R AIL D IN MOU N TIN G C L 2 34 59 4 SC R EWD R IVER SLOT FOR R EMOVAL FR OM T R AIL 4...

Страница 21: ...______________________________________ 21 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 03 AUG 2017 J CAP JAA...

Отзывы: