Acromag IntelliPack 841T Скачать руководство пользователя страница 5

IntelliPack Series 841T Transmitter/Alarm User's Manual                                                                Frequency Input 
___________________________________________________________________________________________ 

 - 5 - 

Table 2:  841T Default Factory Configuration 

PARAMETER 

CONFIGURATION/CALIBRATION 

Input Range 

Frequency 0 to 50KHz 

Samples 

1 (No Input Averaging) 

Resistor 

Pull-Up 

Threshold 

Bipolar 0.0V (zero crossing) 
with +/-25mV Hysteresis 

Event Debounce 

5ms 

Event Edge 

Rising 

Counter Termination 

Auto-Reset 

Output Range 

0 to 10VDC (Jumper Installed) 

Output Mode 

Normal Acting (Ascending Signal) 

Excitation Supply 

8.2V (Use of excitation is optional) 

Relay Mode & Setpoint 

High Limit at 50KHz 

Deadband 

500Hz 

Reset Type 

Automatic Reset (Non-Latching) 

Operating Mode 

Failsafe 

Relay Time Delay 

100ms 

Shaded entries apply to Model 841T-1500 units which also 
include alarm functionality. 
 

Your application may differ from the default configuration and 

will require that the transmitter be reconfigured to suit your needs.  
This is accomplished with Acromag’s user-friendly Windows 
95

/NT

 Configuration Program and Serial Port Adapter.  

Configuration is normally done prior to field installation since field 
configurability via the module’s push-buttons is generally limited 
to zero, full-scale, setpoint, and dropout adjustments (frequency 
inputs only).  See the Transmitter Configuration Manual (8500-
570) for instructions. 
 

Jumper Installation (For Voltage Output Only) 
 

For voltage output, a short jumper must be installed between 

the output “I+” and “JMP” terminals.  A jumper wire is included 
with the unit and is already installed between the output “JMP” 
and “I+” terminals.  Verify the position of this jumper if your 
application requires output voltage.  Remove this jumper for 
current output applications.  Refer to the Electrical Connections 
Drawing 4501-683. 
 

Mounting:  

Refer to Enclosure Dimensions Drawing 4501-642 for 

mounting and clearance dimensions. 

 

DIN Rail Mounting:

  This module can be mounted on "T" 

type DIN rails.  Use suitable fastening hardware to secure the 
DIN rail to the mounting surface.  Units may be mounted 
side-by-side on 1-inch centers for limited space applications. 
 

"T" Rail (35mm), Type EN50022:  

To attach a module to this 

style of DIN rail, angle the top of the unit towards the rail and 
locate the top groove of the adapter over the upper lip of the 
rail.  Firmly push the unit towards the rail until it snaps solidly 
into place.  To remove a module, first separate the input 
terminal block(s) from the bottom side of the module to 
create a clearance to the DIN mounting area.  Next, insert a 
screwdriver into the lower arm of the DIN rail connector and 
use it as a lever to force the connector down until the unit 
disengages from the rail. 

Electrical Connections 

 

Terminals can accommodate wire from 12-24 AWG (stranded 

or solid copper).  Strip back wire insulation 1/4-inch on each lead 
before installing into the terminal block.  Input wiring should be 
shielded twisted-pair.  Since common mode voltages can exist on 
signal wiring, adequate wire insulation should be used and proper 
wiring practices followed.  It is recommended that transmitter 
output and power wiring be separated from the input signal wiring 
for safety, as well as for low noise pickup.  Note that input, power, 
output, and relay terminal blocks are a plug-in type and can be 
easily removed to facilitate module removal or replacement 
without removing individual wires.  If your application requires 
voltage output, you must install a jumper between the output 

“I+” 

and “JMP” terminals (jumper is installed at the factory).  Remove 
this jumper for current output applications.  Be sure to remove 
power and/or disable the load before unplugging the terminals to 
uninstall the module, installing or removing jumpers, or before 
attempting service.  All connections must be made with power 
removed. 
 

CAUTION:

  Risk of Electric Shock - More than one 

disconnect switch may be required to de-energize the 
equipment before servicing. 

 
1.

    Power:

  Refer to Electrical Connections Drawing 4501-683.  

Variation in power supply voltage within rated limits has 
negligible effect on module accuracy.  For supply 
connections, use No. 14 AWG wires rated for at least 75

C.  

The power terminal is diode-coupled for reverse polarity 
protection. 

 
2.

   Frequency or Pulse Counting Inputs:  

Connect input(s) per 

Drawing 4501-683.  Observe proper polarity (see label for 
input type).  Excitation  is provided at the input terminals.  For 
TTL or low-side transistor switches, use the on board pullup 
resistor.  For high-side transistor switches (open drain or 
collector), use the on board pull-down resistor.  For dry 
contact switches, use the on-board excitation supply and pull-
up or pull-down resistors, as required. 

 

WARNING:

  If input frequency exceeds the full-scale beyond 

110%, sample aliasing could cause measurement error and 
generate false alarms.  Limit the maximum frequency to less 
than 110% of full-scale to avoid these errors. 

 
3.

   Analog Output Connections

:  Wire outputs as shown in 

Electrical Connections Drawing 4501-683.  For voltage 
output, you must also install a jumper between the output “I+” 
and “JMP” terminals.  Remove this jumper for current output. 

 

Note: 

 For sensitive applications, high frequency noise may 

be reduced by placing a 0.1uF capacitor directly across the 
load. 

 
4.

   Output Relay Contacts (841T-1500 Only)

:  Wire relay 

contacts as shown in Electrical Connections Drawing 4501-
683.  See the “Alarm Relay Specifications” for power 
capacity.  If necessary, an interposing relay can be used to 
switch higher currents as illustrated in Interposing Relay 
Connection Drawing 4501-646.  

Содержание IntelliPack 841T

Страница 1: ...Frequency or Pulse Counting Input USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1997 Acromag Inc Printed in the USA D...

Страница 2: ...T are registered trademarks of Microsoft Corp 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter models listed in Table 1 Supplementary sheets are attached for units w...

Страница 3: ...lity of this device to be reprogrammed many times Convenient Field Reprogrammability Adjustment to transmitter zero and full scale plus alarm setpoint and deadband can be made via module push buttons...

Страница 4: ...he common DB9P serial port connector of a host computer The adapter also has a 6 wire RJ11 phone jack to connect to the IntelliPack alarm module via a separate interconnecting cable described below Re...

Страница 5: ...ages from the rail Electrical Connections Terminals can accommodate wire from 12 24 AWG stranded or solid copper Strip back wire insulation 1 4 inch on each lead before installing into the terminal bl...

Страница 6: ...tage meter is required to monitor the output level This meter must be accurate beyond the module specifications for best results Note The module s input frequency range must already be set via the Int...

Страница 7: ...d Configuration LED Program Indication LED INDICATOR Constant ON FLASHING Yellow Zero Full Scale labeled Z FS Zero Full Scale 841T 1500 Only Yellow Relay labeled RLY High or Low Setpoint High or Low D...

Страница 8: ...rking and powered serial interface adapter Acromag s Application Engineers can provide further technical assistance if required When needed complete repair services are available from Acromag 6 0 SPEC...

Страница 9: ...tion near the upper end of the range thus decreasing effective accuracy in this range Table 6 Input Measurement Alarm Accuracy Nominal Input Range Accuracy at 25 C Accuracy Over Temperature 0 to 100 0...

Страница 10: ...tacts The relay operates as a limit alarm with control of deadband hysteresis latching non latching contacts failsafe non failsafe modes plus relay time delay SPDT Alarm Relay Specifications 841T 1500...

Страница 11: ...static Discharge ESD Immunity Complies with IEC1000 4 2 Level 3 8KV 4KV air direct discharge to the enclosure port and European Norm EN50082 1 Surge Immunity Complies with IEC1000 4 5 Level 3 2 0KV an...

Страница 12: ...t Range Unit can be configured for either a voltage or current output range A jumper must also be installed between the output I and JMP terminals for voltage output remove this jumper for current out...

Страница 13: ...m state or non failsafe operation relay energized in alarm state Failsafe mode provides the same contact closure for alarm states as for power loss while non failsafe mode uses alarm contact closure o...

Страница 14: ...SIENT SUPPRESSION DEVICES NOT SHOWN BRTN INP UT 2 3 2 2 FQ IN 5 V INPUT SIGNAL CONDITIONING HYSTERESIS DIV PD BIPO PUP COMPARATOR SERIES 841T SIMPLIFIED SCHEMATIC UNIP REF 1 5 V INPUT ISOL ATION MODE...

Страница 15: ...ency Pulse Counting Counts Counts ANALOG INPUT MODEL 811T 1500 ONLY PV PV Percent SEN SOR INPUT BLOCK RANGE ADJUST BLOCK PV Transfer Function Linear Proportional Configuration Variables High or Low Li...

Страница 16: ...IntelliPack Series 841T Transmitter Alarm User s Manual Frequency Input ___________________________________________________________________________________________ 16...

Страница 17: ...0 T O 3 6 VDC REL AY CO NNECTIO NS Acromag GROUND T B4 M O D E RE L AY P WR 8 4 1 T 1 5 0 0 REMO TE EXTERNAL CO UNTER RESET SW I T CH OPEN COL L ECT OR SEE T B2 INPUT CONNECT IONS ON PAGE 2 PRACT ICES...

Страница 18: ...T NOT E 2 T HIS GROUND CONNECT ION IS RECOMMENDED F OR BEST USE CAUT I ON AND AVOID MAKING ADDIT IONAL GROUND CONNECT IONS W HICH COUL D GENERAT E GROUND L OOPS AND MEASUREMENT ERROR T B2 E X C E X C...

Страница 19: ...21 24 CONTACT FIGURE A 46 TB4 TB3 GROUND CONTACT FIGURE B RELAY 46 43 45 N O COM 35 42 JMP TB3 PWR 32 34 31 DC V DC 11 14 12 TB2 22 15 25 23 26 DIODE DC LOAD TB4 N C MOV AC LOAD TB4 N C SPDT CONTACTS...

Страница 20: ...________________________________ 20 RUN Acromag RLY S T Z FS 118 9 4 68 95 3 3 75 MODE S E T D IN EN 50022 35mm T R AIL D IN MOU N TIN G C L 2 34 59 4 SC R EWD R IVER SLOT FOR R EMOVAL FR OM T R AIL 4...

Страница 21: ...______________________________________ 21 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 03 AUG 2017 J CAP JAA...

Отзывы: