5.0  SERVICE AND REPAIR 

 

CAUTION:

  Risk of Electric Shock - More than one 

disconnect switch may be required to de-energize the 
equipment before servicing. 

 

SERVICE AND REPAIR ASSISTANCE 

 

This module contains solid-state components and requires no 

maintenance, except for periodic cleaning and transmitter 
configuration parameter (zero, full-scale, setpoint, deadband, etc) 
verification.  Since Surface Mounted Technology (SMT) boards 
are generally difficult to repair, it is highly recommended that a 
non-functioning module be returned to Acromag for repair.  The 
board can be damaged unless special SMT repair and service 
tools are used.  Further, Acromag has automated test equipment 
that thoroughly checks and calibrates the performance of each 
module.  Please refer to Acromag’s Service Policy Bulletin or 
contact Acromag for information on service parts and repair. 

 

PRELIMINARY SERVICE PROCEDURE 

 
Before beginning repair, be sure that all installation and 

configuration procedures have been followed.  The unit routinely 
performs internal diagnostics following power-up or reset.  During 
this period, all LED’s will turn ON momentarily, and the green 
“Run” LED flashes.  If the diagnostics complete successfully, the 
“Run” LED will stop flashing after approximately one second and 
remain ON.  This indicates that the unit is operating normally.  If 
the “Run” LED continues to flash, then this is indicative of a 
problem.  In this case, use the Acromag IntelliPack Configuration 
Software to reconfigure the module or download its firmware and 
this will usually cure the problem.  If the diagnostics continue to 
indicate a problem (a continuously flashing green LED), or if other 
evidence points to a problem with the unit, an effective and 
convenient fault diagnosis method is to exchange the 
questionable module with a known good unit. 

 
The IntelliPack Serial Port Adapter also contains a red LED 

visible at the small opening in the enclosure to the right of the 
RJ11 receptacle.  If this LED is OFF or Flashing and power is 
ON, then a communication interface problem exists.  Note that 
the adapter receives its power from the IntelliPack module.  A 
constant ON LED indicates a properly working and powered 
serial interface adapter. 

 
Acromag’s Application Engineers can provide further 

technical assistance if required.  When needed, complete repair 
services are available from Acromag. 
 

 

6.0  SPECIFICATIONS 

 

841T-1500-C

, Frequency/Pulse Input, I/V Output, SPDT Relay 

841T-0500-C

, Frequency/Pulse Input, I/V Output 

 

General:

  The IntelliPack Model 841T-0500 is a DC-powered 

transmitter which conditions a single frequency or pulse count 
input, and provides an isolated voltage or current output.  
Isolation is supplied between the sensor input, the output, 
and power.  The 841T-1500 adds a SPDT, Form C, electro-
mechanical relay, which provides a local limit alarm function 
with isolated relay contacts.  This transmitter/alarm is DIN-rail 
mounted.   

 

The unit is configured and calibrated with our user-friendly 
Windows 95

 or NT

 IntelliPack Configuration Program.  

Push-buttons on the module allow adjustment to the zero and 
full-scale points for the transmitter, plus setpoint and 
deadband adjustment for modules with the alarm option.  All 
calibration and configuration information is stored in non-
volatile reprogrammable memory in the module. 

 
 

MODEL NUMBER DEFINITION 
 

Transmitters are color coded with a white label.  The prefix 

“8” denotes the IntelliPack Series 800, while the “T” suffix 
specifies that this device is primarily a process transmitter. 

 

841T: 

  Transmits and isolates a single frequency or pulse 

counting input. 

 

-X500:

  The four digits of this model suffix represent the following 

options, respectively: 

 

X = 1 with Alarm Relay, X = 0 without Alarm Relay; 
5 = Output: Transmitter Voltage or Current; 
0 = Enclosure: DIN rail mount; 
0 = Approvals: cULus Listed. 

 
 

INPUT SPECIFICATIONS 

 

Unit must be wired and configured for the intended input type 

and range (see Installation Section for details).  The following 
paragraphs summarize this model’s input types, ranges, and 
applicable specifications. 

 
Frequency Input:

  Select 0 to 100.00Hz, 0 to 1000.0Hz, or 0 to 

50KHz.  Unit accepts unipolar or bipolar (zero crossing) input 
signals.  Frequency is accurately measured to a minimum of 
1Hz (50KHz range), or 0.5Hz (100Hz & 1KHz ranges).  
Unmeasurable input frequencies below 1Hz are represented 
as 0Hz.  Status LED will flash if input frequency is 
unmeasurable (below 1Hz), or if the signal amplitude is 
insufficient for detection.   

Pulse Counter Input:

  100Hz maximum counting rate.  Minimum 

pulse width is 5ms (5ms ON and 5ms OFF for 10ms period or 
100Hz).  Pulse count range is 0 to 65535 pulses.  Unit 
accepts unipolar or bipolar input pulses and samples the 
input at a 1.2ms rate. 

Содержание IntelliPack 841T

Страница 1: ...Frequency or Pulse Counting Input USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1997 Acromag Inc Printed in the USA D...

Страница 2: ...T are registered trademarks of Microsoft Corp 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter models listed in Table 1 Supplementary sheets are attached for units w...

Страница 3: ...lity of this device to be reprogrammed many times Convenient Field Reprogrammability Adjustment to transmitter zero and full scale plus alarm setpoint and deadband can be made via module push buttons...

Страница 4: ...he common DB9P serial port connector of a host computer The adapter also has a 6 wire RJ11 phone jack to connect to the IntelliPack alarm module via a separate interconnecting cable described below Re...

Страница 5: ...ages from the rail Electrical Connections Terminals can accommodate wire from 12 24 AWG stranded or solid copper Strip back wire insulation 1 4 inch on each lead before installing into the terminal bl...

Страница 6: ...tage meter is required to monitor the output level This meter must be accurate beyond the module specifications for best results Note The module s input frequency range must already be set via the Int...

Страница 7: ...d Configuration LED Program Indication LED INDICATOR Constant ON FLASHING Yellow Zero Full Scale labeled Z FS Zero Full Scale 841T 1500 Only Yellow Relay labeled RLY High or Low Setpoint High or Low D...

Страница 8: ...rking and powered serial interface adapter Acromag s Application Engineers can provide further technical assistance if required When needed complete repair services are available from Acromag 6 0 SPEC...

Страница 9: ...tion near the upper end of the range thus decreasing effective accuracy in this range Table 6 Input Measurement Alarm Accuracy Nominal Input Range Accuracy at 25 C Accuracy Over Temperature 0 to 100 0...

Страница 10: ...tacts The relay operates as a limit alarm with control of deadband hysteresis latching non latching contacts failsafe non failsafe modes plus relay time delay SPDT Alarm Relay Specifications 841T 1500...

Страница 11: ...static Discharge ESD Immunity Complies with IEC1000 4 2 Level 3 8KV 4KV air direct discharge to the enclosure port and European Norm EN50082 1 Surge Immunity Complies with IEC1000 4 5 Level 3 2 0KV an...

Страница 12: ...t Range Unit can be configured for either a voltage or current output range A jumper must also be installed between the output I and JMP terminals for voltage output remove this jumper for current out...

Страница 13: ...m state or non failsafe operation relay energized in alarm state Failsafe mode provides the same contact closure for alarm states as for power loss while non failsafe mode uses alarm contact closure o...

Страница 14: ...SIENT SUPPRESSION DEVICES NOT SHOWN BRTN INP UT 2 3 2 2 FQ IN 5 V INPUT SIGNAL CONDITIONING HYSTERESIS DIV PD BIPO PUP COMPARATOR SERIES 841T SIMPLIFIED SCHEMATIC UNIP REF 1 5 V INPUT ISOL ATION MODE...

Страница 15: ...ency Pulse Counting Counts Counts ANALOG INPUT MODEL 811T 1500 ONLY PV PV Percent SEN SOR INPUT BLOCK RANGE ADJUST BLOCK PV Transfer Function Linear Proportional Configuration Variables High or Low Li...

Страница 16: ...IntelliPack Series 841T Transmitter Alarm User s Manual Frequency Input ___________________________________________________________________________________________ 16...

Страница 17: ...0 T O 3 6 VDC REL AY CO NNECTIO NS Acromag GROUND T B4 M O D E RE L AY P WR 8 4 1 T 1 5 0 0 REMO TE EXTERNAL CO UNTER RESET SW I T CH OPEN COL L ECT OR SEE T B2 INPUT CONNECT IONS ON PAGE 2 PRACT ICES...

Страница 18: ...T NOT E 2 T HIS GROUND CONNECT ION IS RECOMMENDED F OR BEST USE CAUT I ON AND AVOID MAKING ADDIT IONAL GROUND CONNECT IONS W HICH COUL D GENERAT E GROUND L OOPS AND MEASUREMENT ERROR T B2 E X C E X C...

Страница 19: ...21 24 CONTACT FIGURE A 46 TB4 TB3 GROUND CONTACT FIGURE B RELAY 46 43 45 N O COM 35 42 JMP TB3 PWR 32 34 31 DC V DC 11 14 12 TB2 22 15 25 23 26 DIODE DC LOAD TB4 N C MOV AC LOAD TB4 N C SPDT CONTACTS...

Страница 20: ...________________________________ 20 RUN Acromag RLY S T Z FS 118 9 4 68 95 3 3 75 MODE S E T D IN EN 50022 35mm T R AIL D IN MOU N TIN G C L 2 34 59 4 SC R EWD R IVER SLOT FOR R EMOVAL FR OM T R AIL 4...

Страница 21: ...______________________________________ 21 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 03 AUG 2017 J CAP JAA...

Отзывы: