IntelliPack Series 841T Transmitter/Alarm User's Manual                                                                Frequency Input 
___________________________________________________________________________________________ 

 - 11 - 

ENVIRONMENTAL SPECIFICATIONS 

 
Operating Temperature: 

 -25

C to +70

C (-13

F to +158

F). 

Storage Temperature:  

-40

C to +85

C (-40

F to +185

F). 

Relative Humidity:

  5 to 95%, non-condensing. 

Power Requirements:

  +10V Minimum to +36V DC Maximum.  

Current draw is a function of supply voltage (see Table 8).  
Current shown in Table 8 assumes that the input excitation 
supply is delivering 24mA, the output circuit is at 20mA, and 
the IntelliPack Serial Interface Adapter is connected.  For 
841T-1500 units, the current shown also assumes that the 
alarm relay is energized. An internal diode provides reverse 
polarity protection.  

 

CAUTION:

  Do not exceed 36VDC peak, to avoid 

                   damage to the module.

 

 
Table 8:  841T Supply Current 

Supply 

Voltage 

Model 

841T-0500 

Model 841T-1500 

(Relay Energized) 

10V 

225mA 

265mA 

12V 

180mA 

205mA 

15V 

145mA 

160mA 

24V 

95mA 

100mA 

36V 

70mA 

75mA 

Note:

  Disconnecting the Serial Port Adapter will reduce 

current draw 7% on average, while unloading the input 
excitation supply will reduce current consumption about 12%. 

 

IMPORTANT 

– External Fuse:

  If unit is powered from a supply 

capable of delivering more than 1A to the unit, it is recommended 
that this current be limited via a high surge tolerant fuse rated for 
a maximum current of 1A or less (for example, see Bel Fuse 
MJS1). 
 

Power Supply Effect:   

DC Volts:  

Less than 

0.001% of output span change per 

volt DC for rated power supply variations. 

60/120 Hz Ripple:

  Less than 0.01% of output span per volt 

peak-to-peak of power supply ripple. 

Isolation: 

 Input, power, output, and optional relay output circuits 

are isolated from each other for common-mode voltages up 
to 250VAC, or 354V DC off DC power ground, on a 
continuous basis (will withstand 1500VAC dielectric strength 
test for one minute without breakdown).  This complies with 
test requirements outlined in ANSI/ISA-82.01-1988 for the 
voltage rating specified.  

Installation Category:

  Suitable for installation in a Pollution 

Degree 2 environment with installation category (over-voltage 
category) II rating. 

Radiated Field Immunity (RFI):

  Complies with IEC1000-4-3 

Level 3 (10V/M, 80 to 1000MHz AM & 900MHz keyed) and 
European Norm EN50082-1. 

Electromagnetic Interference Immunity (EMI):

  No relay trips 

will occur beyond 

0.25% of input span from setpoint and no 

output shifts 

 0.25% of output span will occur under the 

influence of EMI from switching solenoids, commutator 
motors, and drill motors. 

Electrical Fast Transient Immunity (EFT):

  Complies with 

IEC1000-4-4 Level 3 (2KV power; 1KV signal lines) and 
European Norm EN50082-1. 

Electrostatic Discharge (ESD) Immunity:  

Complies with 

IEC1000-4-2 Level 3 (8KV/4KV air/direct discharge) to the 
enclosure port and European Norm EN50082-1. 

Surge Immunity:  

Complies with IEC1000-4-5 Level 3 (2.0KV) 

and European Norm EN50082-1. 

Radiated Emissions:  

Meets or exceeds European Norm 

EN50081-1 for class B equipment. 

 
 

FIELD CONFIGURATION AND CONTROLS 

 

In-field program capability of transmitter zero & full-scale (all 

models), plus alarm setpoint & dropout levels (841T-1500 only), 
is accomplished with module push-buttons and LED indicators 
(frequency input types only).  This is useful for making 
adjustments in the absence of a host computer.  

Note:

 The unit 

must first be configured using the Configuration Software before 
its configuration can be changed in the field.  Pulse counting 
input parameters cannot be changed in the field via the module 
push-buttons. 

 

Module Push Buttons (See Drawing 4501-642 for Location): 

Mode - 

Used to change mode of field configuration.

 

Set - 

Used to accept input data during field configuration. 

Up - 

Used to increment output level during field configuration.  

Used to reset a latched alarm relay in operating mode. 

Down - 

Used to decrement output level during field 

configuration.  Used to reset a latched alarm relay in 
operating mode. 

LED Indicators (See Drawing 4501-642 for Location): 

Operating (Run) Mode 
Run (Green) -

 Constant ON indicates power is applied and 

unit is operating normally. Upon power up, the module 
may take up to 20 seconds to perform internal 
diagnostics, during diagnostics, the relay may cycle 
states before the module becomes operational. Flashing 
ON/OFF indicates unit is performing diagnostics (first 
second following power-up), or has failed diagnostics 
(after a few seconds). 

Zero/Full-Scale (Yellow) -

 Turned OFF in Run mode. 

Relay (Yellow) - 

Constant ON indicates alarm condition for 

relay.  During field configuration, this LED has a different 
function (see below). 

Status (Yellow) -

 Flashes if input frequency is unmeasurable 

(below 1Hz), or if input amplitude is insufficient for 
detection.  Frequencies less than 1Hz (50KHz range) or 
0.5Hz (100 & 1000Hz ranges) are interpreted as 0Hz. 

Field Configuration Mode (Frequency Inputs Only)

 

Run (Green) -

 OFF in this mode. 

Zero/Full-Scale (Yellow) - 

ON or FLASHING if zero or  

full-scale is being adjusted in this mode (See Table 4). 

Relay (Yellow) - 

ON or FLASHING if alarm setpoint or 

dropout is being adjusted in this mode (See Table 4). 

Status (Yellow) - 

Blinks each time “SET” is pressed to 

capture an I/O signal in this mode. 

 
 

HOST COMPUTER COMMUNICATION 

 

Host Computer Communication:  

Configuration information 

is downloaded from the host computer through one of its 
EIA232 serial ports.  This port must be connected to the 
module through an Acromag IntelliPack Serial Port 
Adapter,

 

which serves as an isolated interface converter 

between EIA232 and the IntelliPack SPI port (standard 
RJ11 6-wire phone jack). 

Baud Rate (EIA232):

  19.2K baud. 

Содержание IntelliPack 841T

Страница 1: ...Frequency or Pulse Counting Input USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1997 Acromag Inc Printed in the USA D...

Страница 2: ...T are registered trademarks of Microsoft Corp 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter models listed in Table 1 Supplementary sheets are attached for units w...

Страница 3: ...lity of this device to be reprogrammed many times Convenient Field Reprogrammability Adjustment to transmitter zero and full scale plus alarm setpoint and deadband can be made via module push buttons...

Страница 4: ...he common DB9P serial port connector of a host computer The adapter also has a 6 wire RJ11 phone jack to connect to the IntelliPack alarm module via a separate interconnecting cable described below Re...

Страница 5: ...ages from the rail Electrical Connections Terminals can accommodate wire from 12 24 AWG stranded or solid copper Strip back wire insulation 1 4 inch on each lead before installing into the terminal bl...

Страница 6: ...tage meter is required to monitor the output level This meter must be accurate beyond the module specifications for best results Note The module s input frequency range must already be set via the Int...

Страница 7: ...d Configuration LED Program Indication LED INDICATOR Constant ON FLASHING Yellow Zero Full Scale labeled Z FS Zero Full Scale 841T 1500 Only Yellow Relay labeled RLY High or Low Setpoint High or Low D...

Страница 8: ...rking and powered serial interface adapter Acromag s Application Engineers can provide further technical assistance if required When needed complete repair services are available from Acromag 6 0 SPEC...

Страница 9: ...tion near the upper end of the range thus decreasing effective accuracy in this range Table 6 Input Measurement Alarm Accuracy Nominal Input Range Accuracy at 25 C Accuracy Over Temperature 0 to 100 0...

Страница 10: ...tacts The relay operates as a limit alarm with control of deadband hysteresis latching non latching contacts failsafe non failsafe modes plus relay time delay SPDT Alarm Relay Specifications 841T 1500...

Страница 11: ...static Discharge ESD Immunity Complies with IEC1000 4 2 Level 3 8KV 4KV air direct discharge to the enclosure port and European Norm EN50082 1 Surge Immunity Complies with IEC1000 4 5 Level 3 2 0KV an...

Страница 12: ...t Range Unit can be configured for either a voltage or current output range A jumper must also be installed between the output I and JMP terminals for voltage output remove this jumper for current out...

Страница 13: ...m state or non failsafe operation relay energized in alarm state Failsafe mode provides the same contact closure for alarm states as for power loss while non failsafe mode uses alarm contact closure o...

Страница 14: ...SIENT SUPPRESSION DEVICES NOT SHOWN BRTN INP UT 2 3 2 2 FQ IN 5 V INPUT SIGNAL CONDITIONING HYSTERESIS DIV PD BIPO PUP COMPARATOR SERIES 841T SIMPLIFIED SCHEMATIC UNIP REF 1 5 V INPUT ISOL ATION MODE...

Страница 15: ...ency Pulse Counting Counts Counts ANALOG INPUT MODEL 811T 1500 ONLY PV PV Percent SEN SOR INPUT BLOCK RANGE ADJUST BLOCK PV Transfer Function Linear Proportional Configuration Variables High or Low Li...

Страница 16: ...IntelliPack Series 841T Transmitter Alarm User s Manual Frequency Input ___________________________________________________________________________________________ 16...

Страница 17: ...0 T O 3 6 VDC REL AY CO NNECTIO NS Acromag GROUND T B4 M O D E RE L AY P WR 8 4 1 T 1 5 0 0 REMO TE EXTERNAL CO UNTER RESET SW I T CH OPEN COL L ECT OR SEE T B2 INPUT CONNECT IONS ON PAGE 2 PRACT ICES...

Страница 18: ...T NOT E 2 T HIS GROUND CONNECT ION IS RECOMMENDED F OR BEST USE CAUT I ON AND AVOID MAKING ADDIT IONAL GROUND CONNECT IONS W HICH COUL D GENERAT E GROUND L OOPS AND MEASUREMENT ERROR T B2 E X C E X C...

Страница 19: ...21 24 CONTACT FIGURE A 46 TB4 TB3 GROUND CONTACT FIGURE B RELAY 46 43 45 N O COM 35 42 JMP TB3 PWR 32 34 31 DC V DC 11 14 12 TB2 22 15 25 23 26 DIODE DC LOAD TB4 N C MOV AC LOAD TB4 N C SPDT CONTACTS...

Страница 20: ...________________________________ 20 RUN Acromag RLY S T Z FS 118 9 4 68 95 3 3 75 MODE S E T D IN EN 50022 35mm T R AIL D IN MOU N TIN G C L 2 34 59 4 SC R EWD R IVER SLOT FOR R EMOVAL FR OM T R AIL 4...

Страница 21: ...______________________________________ 21 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 03 AUG 2017 J CAP JAA...

Отзывы: