Acromag IntelliPack 841T Скачать руководство пользователя страница 7

IntelliPack Series 841T Transmitter/Alarm User's Manual                                                                Frequency Input 
___________________________________________________________________________________________ 

 - 7 - 

Transmitter/Alarm Field Programming Procedure…continued 
 

9.     Press the

 

“UP”

 or

 

“DOWN”

 push-button one time to cause 

the module to auto-adjust its output level to the 
corresponding full-scale output for the output range 
selected.  If the output is not exactly at the full-scale level, 
then each successive depression 

of the “UP” or “DOWN” 

switch will increment or decrement the output signal by a 
small amount.  Holding the switch depressed will increase 
the amount of increment or decrement. 

10.   Press the 

“SET”

 push-button to accept the full-scale value.  

Note every ti

me “SET” is pressed, the yellow “Status” LED 

will flash once and the full-scale output will be captured. 

11.   If configuring an 841T-0500 model which has no alarm 

function, skip steps 12-17 and jump ahead to step 18. 

12.   Press the 

“MODE”

 push button one time until the yellow 

zero/full-scale LED goes out and the yellow relay LED turns 
ON (see Table 4).  In this mode, the unit is ready to accept 
an input setpoint level for the alarm.  If you do not wish to 
change the setpoint, skip to step 15. 

13.   Adjust input source to the High or Low alarm setpoint level. 
14.   Press the

 

“SET”

 push button to accept the setpoint.  Note 

every time “SET” button is pressed, the yellow status LED 
will flash once and the value at the input will be captured. 

15.   Press the

 

“MODE”

 push button one time and the yellow 

relay LED should start flashing (see Table 4).  This means 
the unit is ready to accept the dropout level for the alarm.  If 
you do not wish to change the dropout, skip to step 18. 

16.   Adjust the input frequency to the desired dropout level.  
17.   Press the

 

“SET”

 push button to accept the input dropout 

level.  Note every time “SET” is pressed, the yellow status 
LED will flash once and the value at the input will be 
captured.  The module will use the difference between the 
setpoint and dropout values to calculate relative deadband. 

18.   Press the

 

“MODE”

 push button one time to complete the 

program sequence and return to run mode.  The green 
“RUN” LED will turn ON, the yellow “Zero/Full-Scale” LED 
will be OFF, and the yellow alarm LED will be ON or OFF 
according to the alarm status.  The module will now assume 
a transfer function based on the zero and full-scale values 
just set.  The setpoint and dropout of 841T-1500 units is 
used to determine the alarm deadband.  Note that until 
“SET” is pressed, pushing “MODE” will only toggle between 
the zero & full-scale, plus setpoint & dropout adjustment 
modes (841T-1500 units), without affecting their values.  
Further, if no push-buttons are depressed for a period 
greater than 2 minutes, then the module will automatically 
revert to run mode (green “Run” LED will light) and no 
changes will be made to the original zero, full-scale, and 
optional setpoint & dropout settings. 

 

Notes (Field Program Procedure): 

 
1.   In field configuration mode, the yellow zero/full-scale LED 

(Z/FS) and relay LED (RLY) are used to indicate which 
program parameter is being adjusted as illustrated in Table 3: 

 
Table 3:  Field Configuration LED Program Indication 

LED INDICATOR 

Constant ON 

FLASHING 

Yellow Zero/Full-Scale 

(labeled “Z/FS”) 

 

Zero 

 

Full-Scale 

841T-1500 Only

 

Yellow Relay 

(labeled “RLY”), 

 

High or Low 

Setpoint 

 

High or Low 

Dropout 

 

Notes (Field Program Procedure)…continued: 

 
2.   To summarize, the green “Run” LED is turned off in field 

configuration mode.  The yellow zero/full-scale LED is ON or 
FLASHING when the corresponding zero or full-scale value is 
being set in field configuration mode and turned OFF in run 
mode.  The yellow alarm LED is ON or FLASHING when the 
corresponding setpoint or dropout/deadband level is being set 
in field configuration mode. 

3.   If the transmitter/alarm is in field configuration mode and no 

push buttons are pressed after 2 minutes, then the module  
will return to the run mode, the green “Run” LED will light, and 
no changes to any program parameters will be made. 

4.   Latching alarms require a push button reset to exit the alarm 

state (this may also be accomplished under software control).  
Use the up or down push-button on the front of the module to 
reset a latched alarm relay. 

 
 

4.0  THEORY OF OPERATION 

 

Refer to the Block Diagram of Drawing 4501-682 and  

4501-692 to gain a better understanding of the circuit.  Note that 
these transmitters use a comparator and logic gate to convert the 
input signal into a digital pulse stream.  The comparator is used 
to provide the threshold and hysteresis, while the logic gate is 
used to “square” the waveshape.  The microcontroller samples 
the input pulse stream while tracking the number of internal 
sampling clock cycles to determine the period of the input signal 
and derive its frequency.  The sampling clock rate is 666666.667 
cycles per second, or 1.5us per cycle.  For frequencies below 
100Hz, the number of sampling clock cycles in one input wave 
cycle is used to determine the period of the input.  For 
frequencies in the range of 100Hz to 1000Hz, the number of 
sampling clock cycles in eight input wave cycles is used to 
determine the input period.  As such, internal resolution 
decreases with increasing frequency and is generally better than 
the display resolution for the range, except near the upper end of 
the 100Hz and 1000Hz ranges, where it approaches half the 
display resolution for these ranges.  For the 50KHz range, the 
number of input wave cycles in a gated 1 second period is used 
to calculate the input period.  The microcontroller will compute 
the input frequency and complete the transfer equation according 
to the transmitter type and its embedded function.  It sends a 
corresponding output signal to an optically isolated Digital-to-
Analog Converter (DAC).  The DAC then updates its current or 
voltage outputs in response.  The microcontroller also compares 
the signal value to the limit value and completes all necessary 
alarm functions per its embedded program (841T-1500 units 
only).  The embedded configuration and calibration parameters 
are stored in non-volatile memory integrated within the 
microcontroller.  Only the functions required by an application are 
actually stored in memory

—new functionality can be downloaded 

via the IntelliPack Configuration Program and Serial Port Adapter.  
A wide input switching regulator (isolated flyback mode) provides 
is5V and +16V power to the circuit, plus an is15V 
output circuit supply. 

 

Содержание IntelliPack 841T

Страница 1: ...Frequency or Pulse Counting Input USER S MANUAL ACROMAG INCORPORATED 30765 South Wixom Road Wixom MI 48393 2417 U S A Tel 248 295 0880 Fax 248 624 9234 Copyright 1997 Acromag Inc Printed in the USA D...

Страница 2: ...T are registered trademarks of Microsoft Corp 1 0 INTRODUCTION These instructions cover hardware functionality of the transmitter models listed in Table 1 Supplementary sheets are attached for units w...

Страница 3: ...lity of this device to be reprogrammed many times Convenient Field Reprogrammability Adjustment to transmitter zero and full scale plus alarm setpoint and deadband can be made via module push buttons...

Страница 4: ...he common DB9P serial port connector of a host computer The adapter also has a 6 wire RJ11 phone jack to connect to the IntelliPack alarm module via a separate interconnecting cable described below Re...

Страница 5: ...ages from the rail Electrical Connections Terminals can accommodate wire from 12 24 AWG stranded or solid copper Strip back wire insulation 1 4 inch on each lead before installing into the terminal bl...

Страница 6: ...tage meter is required to monitor the output level This meter must be accurate beyond the module specifications for best results Note The module s input frequency range must already be set via the Int...

Страница 7: ...d Configuration LED Program Indication LED INDICATOR Constant ON FLASHING Yellow Zero Full Scale labeled Z FS Zero Full Scale 841T 1500 Only Yellow Relay labeled RLY High or Low Setpoint High or Low D...

Страница 8: ...rking and powered serial interface adapter Acromag s Application Engineers can provide further technical assistance if required When needed complete repair services are available from Acromag 6 0 SPEC...

Страница 9: ...tion near the upper end of the range thus decreasing effective accuracy in this range Table 6 Input Measurement Alarm Accuracy Nominal Input Range Accuracy at 25 C Accuracy Over Temperature 0 to 100 0...

Страница 10: ...tacts The relay operates as a limit alarm with control of deadband hysteresis latching non latching contacts failsafe non failsafe modes plus relay time delay SPDT Alarm Relay Specifications 841T 1500...

Страница 11: ...static Discharge ESD Immunity Complies with IEC1000 4 2 Level 3 8KV 4KV air direct discharge to the enclosure port and European Norm EN50082 1 Surge Immunity Complies with IEC1000 4 5 Level 3 2 0KV an...

Страница 12: ...t Range Unit can be configured for either a voltage or current output range A jumper must also be installed between the output I and JMP terminals for voltage output remove this jumper for current out...

Страница 13: ...m state or non failsafe operation relay energized in alarm state Failsafe mode provides the same contact closure for alarm states as for power loss while non failsafe mode uses alarm contact closure o...

Страница 14: ...SIENT SUPPRESSION DEVICES NOT SHOWN BRTN INP UT 2 3 2 2 FQ IN 5 V INPUT SIGNAL CONDITIONING HYSTERESIS DIV PD BIPO PUP COMPARATOR SERIES 841T SIMPLIFIED SCHEMATIC UNIP REF 1 5 V INPUT ISOL ATION MODE...

Страница 15: ...ency Pulse Counting Counts Counts ANALOG INPUT MODEL 811T 1500 ONLY PV PV Percent SEN SOR INPUT BLOCK RANGE ADJUST BLOCK PV Transfer Function Linear Proportional Configuration Variables High or Low Li...

Страница 16: ...IntelliPack Series 841T Transmitter Alarm User s Manual Frequency Input ___________________________________________________________________________________________ 16...

Страница 17: ...0 T O 3 6 VDC REL AY CO NNECTIO NS Acromag GROUND T B4 M O D E RE L AY P WR 8 4 1 T 1 5 0 0 REMO TE EXTERNAL CO UNTER RESET SW I T CH OPEN COL L ECT OR SEE T B2 INPUT CONNECT IONS ON PAGE 2 PRACT ICES...

Страница 18: ...T NOT E 2 T HIS GROUND CONNECT ION IS RECOMMENDED F OR BEST USE CAUT I ON AND AVOID MAKING ADDIT IONAL GROUND CONNECT IONS W HICH COUL D GENERAT E GROUND L OOPS AND MEASUREMENT ERROR T B2 E X C E X C...

Страница 19: ...21 24 CONTACT FIGURE A 46 TB4 TB3 GROUND CONTACT FIGURE B RELAY 46 43 45 N O COM 35 42 JMP TB3 PWR 32 34 31 DC V DC 11 14 12 TB2 22 15 25 23 26 DIODE DC LOAD TB4 N C MOV AC LOAD TB4 N C SPDT CONTACTS...

Страница 20: ...________________________________ 20 RUN Acromag RLY S T Z FS 118 9 4 68 95 3 3 75 MODE S E T D IN EN 50022 35mm T R AIL D IN MOU N TIN G C L 2 34 59 4 SC R EWD R IVER SLOT FOR R EMOVAL FR OM T R AIL 4...

Страница 21: ...______________________________________ 21 Revision History The following table details the revision history for this document Release Date Version EGR DOC Description of Revision 03 AUG 2017 J CAP JAA...

Отзывы: