16
20
hour
(
L
)
R/W
0~23
21
0026H
minute
(
H
)
R/W
0~59
word
22
second
(
L
)
R/W
0~59
23
0021H~002CH
Reserved
24
002DH
No.1
SOE
Record type
R
0: alarm, 1: warning
word
25
002EH
Actual value of
alarm
R
0~30000mA
word
26
002FH
Alarm setting
value
R
10~30000mA
word
27
0030H
Year (H)
R
Alarm time - year
word
28
Month (L)
R
Alarm time - month
29
0031H
Day (H)
R
Alarm time - day
word
30
Hour (L)
R
Alarm time - hour
31
0032H
Minute (H)
R
Alarm time - minute
word
32
Second (L)
R
Alarm time - second
33
0033H~00C2H
Others 24 SOEs
R
The format same as No.1 SOE
Note
:
H represents the upper 8 bits. L represents the lower 8 bits.
8.4 001CH data parsing
The parameter of address 001CH represents the current setting value, as shown in the table below.
High 8 bit
Bit15
Bit14
Bit13
Bit12
Bit11
Bit10
Bit9
Bit8
Low 8 bit
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Bit0
0
Relay AL2 terminals 10 and 9 are normally open by default
1
Relay ALl2 terminals 10 and 9 are normally closed by
default
Bit1
0
The terminals 97 and 96 of relay are normally closed by
default and 96 and 95 are normally open by default
1
The terminals 97 and 96 of relay are normally open by
default and 96 and 95 are normally closed by default
Bit2
0
Manual reset
1
Automatic reset
9 Ordering example
example
:
Auxiliary power supply AC 220V/50Hz
Rated current In
:
80A
model selection
residual current operated relay: ASJ10-LD1C; residual current transformer: AKH-0.66L-L45
effective