9
1~9999 seconds. Unit: 1 second
PASS
1~9999
none
Password setting
TimE
Year, month, day, hour,
minute
Modify time
Time setting
Clr
yes/no
none
Yes: clear the event log
Mod menu instructions
:
After entering the first level menu, short press PROG key to enter the second level menu, Td/+
key and Td/- key are used to switch channels between the second level menu, then press PROG key,
use Td/+ key and Td/- key to modify the specific value. When you're done, press PROG or RESET
to return. After the modification is completed, press RESET key to exit. Before exiting, you should
choose whether to save or not. Press the RESET key again to avoid saving and press PRGO key to
save (when setting the real-time time, it will be saved after modified).
The default return value of alarm and prewarning operating current is 85%. When the leakage
current is less than 85% of the rated residual operating current, the alarm relay AL1 is reset, and
when the leakage current is less than 85% of the rated prewarning residual operating current, the
prewarning relay AL2 reset (the instrument should be set to automatic reset mode).
7.1 Programming Example
The following is a few programming diagrams, users can refer to these examples to program
menu items of the same level.
1
)
View SOE records in running mode
Bit2
0
Manual reset
1
Automatic reset
Bit1
0
Relay AL1 terminals 97,96 are normally closed by default,
96,95 are normally open by default
1
Relay AL1 terminals 97,96 are normally open by default, 96,95
are normally closed by default
Bit0
0
Relay AL2 terminals 10 and 9 are normally open by default
1
Relay AL2 terminals 10 and 9 are normally closed by default
runing
SOE
records
Press PROG
Press Td/+ or Td/-