6
3
Disconnected
alarm light
Red indicator light, it lights when the external
transformer is disconnected
ASJ10L-LD1A
4
Test key
In normal operation, press key for 2s, then the
current channel relay will operate, backlight will
turn red, and alarms will be output. used to check
the relay and alarm trip
5
Reset key
In operation mode, used to relieve relay operation;
In programming mode, used to return to previous
menu or mode.
6
Td/- key
In SOE page of operation mode, it is used to view
the fault records;
In programming mode, it is used to enter next
menu or subtract 1 from the value;
7
Td/+ key
In SOE page of operation mode, it is used to view
the fault records;
In programming mode, it is used to back last menu
or add 1 from the value.
Long press the Td/- key and Td/+ key at the same
time, system will start a self-check and reset.
8
PROG key
In operation mode, short press the key to enter
SOE interface;
In programming mode, it is used to select, return,
confirm and save menu item.
9
LCD
The LCD can display the real-time residual current
value, rated residual current setting value, limit
non-driving time setting value and communication
status. The LCD backlight is green in normal
operation. When alarming, the residual current
reaches the alarming value, and the backlight is
red. When the residual current reaches the warning
value, and the backlight is yellow.
Note:
When the rated residual current is set to be 30mA, the action delay time is invalid, and operate immediately by default.
When there is an alarm indication of transformer disconnection, the “TEST” button is locked and invalid.
5.4 Description of Selection
1) The device is mainly used in system protection, as the protection of direct electric shock,
indirect electric shock, electrical fire and hierarchical protection. For directing shock protection only
as supplementary protection, the rated residual operating current at this time does not exceed 30mA.
2) Protective devices must be installed in the following equipment and places: mobile electrical
equipment and hand-held power tools, electrical equipment used in production, electrical and
mechanical equipment in construction sites, electrical equipment installed outdoors, etc. (See
GB13955 for details).
3) The rated remaining operating current shall fully consider the normal leakage current value