background image

15 

Master Send 

Data 

 

Slave Return 

Data 

Address 

01H 

 

Address 

01H 

Function 

10H 

 

Function 

10H 

Start Address 

High byte 

00H 

 

Start Address 

High byte 

00H 

Low byte 

04H 

 

Low byte 

04H 

number of 

Registers 

High byte 

00H 

 

number of 

Registers 

High byte 

00H 

Low byte 

03H 

 

Low byte 

03H 

Bytes 

06H 

 

CRC codes 

Low byte 

31H 

0004H data for 

sending 

High byte 

09H 

 

High byte 

C9H 

Low byte 

0CH 

   

 

 

0005H data for 

sending 

High byte 

01H 

   

 

 

Low byte 

05H 

   

 

 

0006Hdata for 

sending 

High byte 

0CH 

   

 

 

Low byte 

00H 

   

 

 

CR codes 

Low byte 

53H 

   

 

 

High byte 

3FH 

   

 

 

8.3 Communication Address Table 

No. 

Address 

Parameter 

Read/

Write 

Range of value 

Value 

type 

0000H 

Residual current value 

0~30000mA 

word 

0001H~0007H 

retain 

 

 

 

0008H 

Rated  residual  operating 

current setting 

R/W 

10~30000mA 

word 

0009H 

Prewarning 

operating 

current value 

R/W 

10~30000mA 

word 

000AH~000FH 

retain 

 

 

 

0010H 

Limit  non-driving  time 

value 

R/W 

0~10000ms 

word 

0011H~0017H 

retain 

 

 

 

0018H 

Address 

R/W 

1~247 

word 

0019H 

Baud rate 

R/W 

0,1,2,3,4,5            38.4k, 19.2k, 9600, 

4800, 2400, 1200 

word 

10 

001AH 

Disconnection 

alarm 

setting 

R/W 

bit2, bit1, bit0     

000: close 001: open 

word 

11 

001BH 

Alarm status 

bit2,  bit1,  bit0  000:  normal001: 

warning 010: alarm 100: break line 

word 

12 

001CH 

Mode setting 

R/W 

See chapter 8.4 

word 

13 

001DH 

Protection password 

R/W 

0000~9999 (default:0001) 

word 

14 

001EH 

Di status 

bit1, bit0; 01: ch1 10: ch2 

word 

15 

001FH 

Backlight delay 

R/W 

0~9999; 0: lighting, default 60s 

word 

16 

0020H~0023H 

retain 

 

 

 

17 

0024H 

year

H

 

R/W 

00~99: 2000~2099 

word 

18 

month

L

 

R/W 

1~12 

19 

0025H 

day

H

 

R/W 

1~31 

word 

Содержание ASJ Series

Страница 1: ...041 ASJ Series Residual Current Operated Relay Installation and Operation Instruction V1 9 Acrel Co LTD...

Страница 2: ...tions in this operation manual and Acrel does not take responsibility for personal injuries or economic losses caused by ignoring tips of this manual The contents of the manual will be continuously up...

Страница 3: ...ing attention 4 5 Operating Guide 5 5 1 Description of AC type Panel 5 5 2 Description of A type panel 5 5 3 Description of LCD type panel 5 5 4 Description of Selection 6 5 5 Instructions for the sel...

Страница 4: ...Rated residual operating current can be measured Limit non driving time can be set Two sets of relay output With local and remote test and reset functions Guide DIN 35mm ASJ10 LD1A A type residual cu...

Страница 5: ...0 0 06 0 1 0 2 0 3 0 5 0 8 1 4 10 s note 4 Rated residual non operating current I no 50 I n 50 I n Performance characteristics Sinusoidal AC Sinusoidal AC and pulsating DC Frequency 50Hz 5Hz 50Hz 5Hz...

Страница 6: ...1 Installation Steps ASJ20 series instrument installation method is panel installation both sides of the buckle extrusion fixed the specific operation is as follows 1 On the switchboard choose the ap...

Страница 7: ...xiliary power supply and signal input terminal Auxiliary power supply Signal input 4 3 2 Switching quantity input output terminal DI1 DI2 COM1 24 25 33 Relay output terminal Switching input terminal n...

Страница 8: ...t button To reset the system 3 Alarm light Lights when the rated residual operating current I n is exceeded 4 Test button To test whether the indicator light is normal and the relay can operate normal...

Страница 9: ...ing time setting value and communication status The LCD backlight is green in normal operation When alarming the residual current reaches the alarming value and the backlight is red When the residual...

Страница 10: ...nded The earth fault current is very small and difficult to be estimated operating current can not be reached and the hazardous voltage will appear on the shell TN S system ASJ can be used cut off the...

Страница 11: ...and next section only applies to ASJ10L LD1A First Menu Second Menu Third menu Descriptions Addr 1 247 none Address setting bAUd 1200 2400 4800 9600 19200 38400 none Communication Baud rate setting AL...

Страница 12: ...turn value of alarm and prewarning operating current is 85 When the leakage current is less than 85 of the rated residual operating current the alarm relay AL1 is reset and when the leakage current is...

Страница 13: ...irst event record is generated by the residual current alarm action the alarm value is 200 mA the occurrence time is 11 03 12 08 2 Set the residual current operating value to 50mA _ represents the mod...

Страница 14: ...0ms Long press PROG Press Td to modify Press Td to modify number password confirm press PROG Press PROG Press RESET Press Td Press PROG Press RESET Press Td or Td Press PROG Press Td Running PASS Addr...

Страница 15: ...Press PROG Press RESET Running PASS XXXX Long press PROG Press Td to modify press Td to modify number password confirm Press PROG Password confirm N Press RESET Addr bAUd AL Td 1 247 Press RESET Pres...

Страница 16: ...byte n byte 2 bytes Address code the address code is composed of one byte 8 bit binary at the beginning of the frame and the decimal is 0 255 Only 1 247 is used in the residual current relay and othe...

Страница 17: ...ion there is a method to calculate CRC by using the preset table Its main feature is that the calculation speed is fast but the table needs a large storage space This method will not be described here...

Страница 18: ...H retain 3 0008H Rated residual operating current setting R W 10 30000mA word 4 0009H Prewarning operating current value R W 10 30000mA word 5 000AH 000FH retain 6 0010H Limit non driving time value R...

Страница 19: ...parsing The parameter of address 001CH represents the current setting value as shown in the table below High 8 bit Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8 Low 8 bit Bit7 Bit6 Bit5 Bit4 Bit3 Bit...

Страница 20: ...break line alarm 3 201812 V1 5 Add chapter 4 2 2 4 201912 V1 6 Delete ASJ10L 5 202012 V1 7 Add ASJ10L modify address contact 6 202104 V1 8 Modify AC type output as open Modify some mistake add transf...

Страница 21: ...Fax 0086 21 69158303 Web site www acrel electric com E mail ACREL008 vip 163 com Postcode 201801 Manufacturer Jiangsu Acrel Electrical Manufacturing Co LTD Address No 5 Dongmeng Road Dongmeng industr...

Отзывы: