background image

13 

8

 Communication Guide

 

8.1 Overview of Communication Protocol 

ASJ10L-LD1A/C residual current operated relay uses Modbus-RTU communication protocol. 

The protocol defines check codes, data sequences, etc. in detail, which are necessary for specific 

data exchange. The Modbus-RTU protocol uses a master-slave acknowledgment connection (half 

duplex) on a communication line, which means that signals are transmitted in opposite directions on 

a single communication line. First, the host computer's signal is addressed to the only terminal 

device (slave), then the response signal from the terminal device is transmitted to the host in the 

opposite direction. 

The Modbus-RTU protocol only allows communication between the host (PC, PLC, etc.) and 

terminal devices, and does not allow data exchange between independent terminal devices, so that 

each terminal device does not occupy the communication line when they are initialized, but only 

responds to query signals reaching the local computer. 

8.1.1 Transmission Mode 

The information is transmitted asynchronously and in bytes. The communication information 

transmitted between the master and the slave is in 11-bit word format, which consists of 1 start bit, 8 

data bits (the lowest valid bit is sent first), no check bit, and 1 stop bit. 

8.1.2 Information Frame Format 

Address 

Function 

data 

CRC   

1 byte 

1 byte 

n byte 

2 bytes 

Address code: the address code is composed of one byte (8-bit binary) at the beginning of the 

frame and the decimal is 0-255. Only 1-247 is used in the residual current relay, and other addresses 

are reserved. These bits indicate the address of the user-specified terminal device that will receive 

the host data from it. The address of each terminal device must be unique. Only the terminal to 

which it is addressed will respond to the query containing the address. When the terminal sends back 

a response, the slave address data in the response tells the host which terminal is communicating 

with it. 

Function code: the function code tells the terminal to which it is addressed which function to 

perform. The following table lists the function codes used in this series of instruments as well as 

their significance and function. 

function 

definition 

Function 

03H/04H 

Read 

data 

register 

Get  the  current  binary  value  of  one  or  more 
registers 

10H 

Modify 

multi 

register 

Set  binary  values  into  a  series  of  multiple 
registers 

Data area: the data area contains the data required by the terminal to perform specific functions 

or the data collected when the terminal responds to the query. The contents of the data may be 

values, reference addresses, or set values. For example, the function code tells the terminal to read a 

register, and the data area needs to indicate which register to start from and how many data to read. 

The embedded address and data vary according to the types and the different contents between the 

slaves. 

Содержание ASJ Series

Страница 1: ...041 ASJ Series Residual Current Operated Relay Installation and Operation Instruction V1 9 Acrel Co LTD...

Страница 2: ...tions in this operation manual and Acrel does not take responsibility for personal injuries or economic losses caused by ignoring tips of this manual The contents of the manual will be continuously up...

Страница 3: ...ing attention 4 5 Operating Guide 5 5 1 Description of AC type Panel 5 5 2 Description of A type panel 5 5 3 Description of LCD type panel 5 5 4 Description of Selection 6 5 5 Instructions for the sel...

Страница 4: ...Rated residual operating current can be measured Limit non driving time can be set Two sets of relay output With local and remote test and reset functions Guide DIN 35mm ASJ10 LD1A A type residual cu...

Страница 5: ...0 0 06 0 1 0 2 0 3 0 5 0 8 1 4 10 s note 4 Rated residual non operating current I no 50 I n 50 I n Performance characteristics Sinusoidal AC Sinusoidal AC and pulsating DC Frequency 50Hz 5Hz 50Hz 5Hz...

Страница 6: ...1 Installation Steps ASJ20 series instrument installation method is panel installation both sides of the buckle extrusion fixed the specific operation is as follows 1 On the switchboard choose the ap...

Страница 7: ...xiliary power supply and signal input terminal Auxiliary power supply Signal input 4 3 2 Switching quantity input output terminal DI1 DI2 COM1 24 25 33 Relay output terminal Switching input terminal n...

Страница 8: ...t button To reset the system 3 Alarm light Lights when the rated residual operating current I n is exceeded 4 Test button To test whether the indicator light is normal and the relay can operate normal...

Страница 9: ...ing time setting value and communication status The LCD backlight is green in normal operation When alarming the residual current reaches the alarming value and the backlight is red When the residual...

Страница 10: ...nded The earth fault current is very small and difficult to be estimated operating current can not be reached and the hazardous voltage will appear on the shell TN S system ASJ can be used cut off the...

Страница 11: ...and next section only applies to ASJ10L LD1A First Menu Second Menu Third menu Descriptions Addr 1 247 none Address setting bAUd 1200 2400 4800 9600 19200 38400 none Communication Baud rate setting AL...

Страница 12: ...turn value of alarm and prewarning operating current is 85 When the leakage current is less than 85 of the rated residual operating current the alarm relay AL1 is reset and when the leakage current is...

Страница 13: ...irst event record is generated by the residual current alarm action the alarm value is 200 mA the occurrence time is 11 03 12 08 2 Set the residual current operating value to 50mA _ represents the mod...

Страница 14: ...0ms Long press PROG Press Td to modify Press Td to modify number password confirm press PROG Press PROG Press RESET Press Td Press PROG Press RESET Press Td or Td Press PROG Press Td Running PASS Addr...

Страница 15: ...Press PROG Press RESET Running PASS XXXX Long press PROG Press Td to modify press Td to modify number password confirm Press PROG Password confirm N Press RESET Addr bAUd AL Td 1 247 Press RESET Pres...

Страница 16: ...byte n byte 2 bytes Address code the address code is composed of one byte 8 bit binary at the beginning of the frame and the decimal is 0 255 Only 1 247 is used in the residual current relay and othe...

Страница 17: ...ion there is a method to calculate CRC by using the preset table Its main feature is that the calculation speed is fast but the table needs a large storage space This method will not be described here...

Страница 18: ...H retain 3 0008H Rated residual operating current setting R W 10 30000mA word 4 0009H Prewarning operating current value R W 10 30000mA word 5 000AH 000FH retain 6 0010H Limit non driving time value R...

Страница 19: ...parsing The parameter of address 001CH represents the current setting value as shown in the table below High 8 bit Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8 Low 8 bit Bit7 Bit6 Bit5 Bit4 Bit3 Bit...

Страница 20: ...break line alarm 3 201812 V1 5 Add chapter 4 2 2 4 201912 V1 6 Delete ASJ10L 5 202012 V1 7 Add ASJ10L modify address contact 6 202104 V1 8 Modify AC type output as open Modify some mistake add transf...

Страница 21: ...Fax 0086 21 69158303 Web site www acrel electric com E mail ACREL008 vip 163 com Postcode 201801 Manufacturer Jiangsu Acrel Electrical Manufacturing Co LTD Address No 5 Dongmeng Road Dongmeng industr...

Отзывы: