VALVE SETTINGS SCREEN
Parameter
Range
Default Valve
Configured
Value(1)
Notes
Outlet Temp.
Setpoint
60 to 180o F
120
Can also be changed at Alert/Alarm Screen
Installed Valves
Assignment
Loop #1 or Loop
#2
Per Order
Unless valves are added or deleted from the
system, DO NOT change
Actuator On/Off
On (checked) or
Off
Per Order
For Deactivating Actuator, turn “off”
(typ. For replacement)
BV (Ball Valve)
open
Open (checked)
Or Closed
Checked
Checked
This confirms status of outlet ball valve. If you
close it, e.g. to isolate fixtures or if valve is NOT
in service, uncheck this box.
Valve(s) Selection Sliders
If supplied as a BASyC™, the software is preconfigured for valve model selection. If
Upgrading, please make sure the sliders are selecting the correct model valves.
ALERT/ALARM CONFIGURATION SCREEN
CW Low Limit
35 to 200
o
F
35
o
F
If the CW temp. goes below this value,
an alert will result.(2)
CW High Limit
35 to 200
o
F
130
o
F
If the CW temp. goes above this value,
an alert will result.(2)
HW Low Limit
35 to 200
o
F
110
o
F
If the HW temp. goes below this value,
an alert will result.(2)
HW High Limit
35 to 200
o
F
180
o
F
If the HW temp. goes above this value,
an alert will result.(2)
CW PSI Low Limit
0 to 125 PSI
0 PSI
If the CW press. goes below this value,
an alert will result.(2)
CW PSI High Limit
0 to 125 PSI
80 PSI
If the CW press. goes above this value,
an alert will result.(2)
HW PSI Low Limit
0 to 125 PSI
0 PSI
If the HW press. goes below this value,
an alert will result.(2)
HW PSI High Limit
0 to 125 PSI
80 PSI
If the HW press. goes above this value,
an alert will result.(2)
Outlet PSI Low Limit
0 to 125 psi
0 PSi
If the mixing station outlet press. goes below this
value, an alert will result.(2)
Outlet PSI High Limit
0 to 125
o
F
80 PSI
If the mixing station outlet press. goes above this
value, an alert will result.(2)
Outlet Temp.
Setpoint Max. Limit
35 to 180
o
F
130
o
F
If setpoint is set above this value,
an alert will result.
APPENDIX A:
USER SETTINGS CHART