USER SETTINGS CHART CONTINUED

ALERT/ALARM CONFIGURATION SCREEN

Outlet Temp. 

Setpoint Min. Limit

35 to 180

o

 F

110

o

 F

If setpoint is set below this value, an alert will 

result.

Outlet Temp. 

Setpoint

60 to 180

o

 F

120

o

 F

N/A

Configure at Valve Settings Menu, above

Outlet Temp. 

Low Limit

-15 to -1

o

 F

-7

o

 F

If the outlet temp drops below the setpoint by 

this value, an alarm will result.(2)(3) 

Outlet Temp. 

Low Limit

1 to 15

o

 F

7

o

 F

If the outlet temp goes above the setpoint by 

this value, an alarm will result.(2)(3)

SANITIZATION SCREEN

Sanitization Setpoint

60 to 180

o

 F

120

o

 F

Setpoint changes after safe start confimation

Sanitization Time

.1 to 24 hours

.1 hours

At the end of the Sanitization Time, outlet temp. 

setpoint will return to previous setting

PUMP CONTROL AND DATA SCREEN

Acceptable recirc. 

Loop Setting Min.

60 to 180o F

90° F

If the return temp. goes below this value an alert 

will result (2)

Acceptable recirc. 

Loop Setting Max.

60 to 180o F

130° F

If the return temp. goes above this value an alert 

will result (2)

Recirc Loop Setpoint

70 to 160o F

120° F

If the recirc loop is at or above this temp., the 

pump control relay will deactivate (4)

Deadband

1 to 15o F

3° F

After a pump relay deactivation, the return temp. 

must drop by this value before the relay reacti-

vates.

Temperature 

Feedback

Return Sensor 

(checked) or 

unchecked

Return Sensor

Users that order a Final Fixture sensor will use 

that sensor for the pump control relay (5)

Customization for Automatically Alternating Recirculation Pumps

(CONTACT ACORN FOR AVAILABILITY AND ADDITIONAL INFORMATION)

Pump Make and Model:

Pump Alternating 

Cycle

7, 30, 60

or 90 days

7 days

Pump control signal will alternative between 

control relays

Initiate Pump 

Alternation

Off or On

Off

N/A

If initiated, cycle for next alternation will restart

(1) If factory configured, the factory-set values will be entered here.  If the user is configuring the system on startup, please enter the selected valves in this column.
(2) To simultaneously activate an email or text alert notification, check the appropriate box.  IMPORTANT NOTE: To be able to send email notifications, BASYC™ 

must be connected to a mail server, typically via the Ethernet LAN adapters included with every BASyC™ system.

(3) An alarm for this parameter will result in a relay output.  A common relay output is provided for alarms, another common relay output for alerts. If other 
  configurations are required, please contact Acorn for a quotation.
(4) This capability eliminates any requirements for an AquaStat.  On systems that are intended to operating with a constantly recirculating pump, it is recommended 

that this be used as a pump shut off in the event of an emergency, high temperature, condition.

(5) A Return Sensor is most common for the Pump Relay function.  But if so equipped, a Final Fixture sensor is a more efficient option for pump relay control, plus it 

confirms that all fixtures on the system are at a desired LTHW temperature, a very critical point of data for bather safety and satisfaction.

Содержание BASyC ABMV

Страница 1: ...ional User Interface I N S T A L L A T I O N M A I N T E N A N C E G U I D E DIGITAL MIXING VALVE AND MONITORING SYSTEM BASyC Operating Overview Screen BASyC Control Panel Belimo Acuator Command Stati...

Страница 2: ...or whole building water systems Acorn is proud to continue its track record of providing valves while updating the product line with state of the art technology that keeps people safe Acorn Engineeri...

Страница 3: ...ion Pump by Others 14 Inlet Temperature Sensor 14 Return Temperature Sensor 14 Pressure Sensor 15 Flow and Hot Water BTU Data 15 RECIRCULATION PUMP CONTROL 15 FLOW SENSOR 16 STARTUP 16 ADDING BASyC TO...

Страница 4: ...s in one or two separate temperature loops Temperature control per ASSE 1017 during power failure outlet sensor failure electric actuator or thermostatic sensor failure and or software system reboot B...

Страница 5: ...de kit and requires no change in plumbing piping or system operation Simply install the items included in the kit and your system is ready to go This is an exclusive benefit to purchasers of these sys...

Страница 6: ...ired with 120vac 60hz power Disconnect power before servicing or doing any work within the control cabinet to prevent electrical shock and or equipment damage Make all connections in accordance with n...

Страница 7: ...Inclusion and quantity varies by order CONTROL CABINET A Bypass Valve G Outlet Temperature Pressure Sensors H Test Port J MIXING VALVE B Electronic Actuator C Inlet HW temperature pressure sensors D I...

Страница 8: ...djustment are the responsibility of the installer Optional pre configured units and or start up assistance are available please contact Acorn for details DISCONNECT LEAD THEN REVERSE Mixing Valve Hard...

Страница 9: ...l component Install the upgrade bonnet noting the longer stem that s designed to accept the Belimo Actuator provided in the upgrade kit Electronic Actuator Installation Instructions Ensure that the ac...

Страница 10: ...rovided mounted on a custom SS bracket and is shipped with the mounting hardware required to attach it to the strut framing The bottom of each control cabinet should be positioned so it is in line wit...

Страница 11: ...on the configuration of your single or multi valve mixing assembly NETWORK COMMUNICATIONS Acorn BASyC includes several different types of network interfaces to ensure both versatility and adaptability...

Страница 12: ...N CON TROLS ACORN CON TROLVALVES COM 1 8 0 0 4 8 8 8 9 9 9 12 Refer to this diagram for the model number of your BASyC system Available features will be explained on the following pages BASyC CONFIGUR...

Страница 13: ...ACORN CON TROLS ACORN CON TROLVALVES COM 1 8 0 0 4 8 8 8 9 9 9 13...

Страница 14: ...a high temp safety shutdown in the event that something goes wrong with the system We recommend setting this 10 degrees above the mixing station setpoint Relay Pump Control If equipped with this feat...

Страница 15: ...flow or BTU values at the Operating Overview Screen and using the links that appear RECIRCULATION PUMP CONTROL If equipped with a recirculation pump option your BASyC Mixing Valve Assembly may have be...

Страница 16: ...lush pipes of debris Open the isolation ball valves at the hot cold inlets the outlet and the return Look at T P gauges to make sure pressure is available at each Plug the Acorn BASyC unit into a stan...

Страница 17: ...onds After all these LED s light as expected it will take another 5 10 minutes to boot load software and begin normal operation The first indicator of this is that the D1 LED will light up indicating...

Страница 18: ...ld LCD display controller All units ship from the factory preset with a 4 digit LCD passcode of 0101 to access the system If your system is preconfigured please refer to your documentation or contact...

Страница 19: ...1 Press to enter code and access unit After pressing enter you should see the screen above Navigate to the system settings and then TCP IP settings to see the following above Modify the values accord...

Страница 20: ...b browser from any computer on this local area network If you re not sure how to ping a network do this 1 Open a cmd prompt Start Run cmd 2 Type in the command ping IP Address For example ping 10 1 10...

Страница 21: ...shown in the icon name in case there is more than one BASyC system on the local area network The icons apps can be renamed to something more meaningful such as Building A HW You may want to keep the I...

Страница 22: ...endix A has a list of items available based on the login credentials used The first time you log into each username the system will require a password reset Use passwords that are not easily guessed t...

Страница 23: ...o click on the sensor data view button in the navigation menu shown above This button will take you to the screen shown below At each screen within the software you will see the navigation menu except...

Страница 24: ...second loop if applicable Whenever you re servicing your actuator uncheck the box next to the actuator to disable it electronically The valve remains under thermostatic control at the current setpoint...

Страница 25: ...number of degrees the temperature must drop below the setpoint before the pump is turned on again Dead band prevents relay chatter and fast cycling of the pump a condition that could result in a shor...

Страница 26: ...TE Setting the maximum value below the minimum will trigger an alert and the indictor will change color from green in range to yellow out of range To enable an email alert you check the email checkbox...

Страница 27: ...view in pdf Available user selections for are Time Range Today Last 24 hours Yesterday Week to Date Last week Last 7 days Month to Date Last Month Year to Date Last Year Title Give your report any na...

Страница 28: ...on you aren t sure that all the fixtures served are not fully protected to insure the bather s safety during sanitization select cancel and restart sanitization after the proper safety precautions hav...

Страница 29: ...nt of the outlet sensor all functionality will return OPERATING ACTUATOR MANUALLY To operate the Acorn BASyC electronic actuator manually 1 Make sure there is flow through the valve by opening fixture...

Страница 30: ...oes below this value an alert will result 2 CW High Limit 35 to 200o F 130o F If the CW temp goes above this value an alert will result 2 HW Low Limit 35 to 200o F 110o F If the HW temp goes below thi...

Страница 31: ...Fixture sensor will use that sensor for the pump control relay 5 Customization for Automatically Alternating Recirculation Pumps CONTACT ACORN FOR AVAILABILITY AND ADDITIONAL INFORMATION Pump Make an...

Страница 32: ...ET PRESSURE 0 10 VDC 150 psi TRANSDUCER T4 3 T3 3 U11 GRND HW INLET PRESSURE 0 10 VDC 150 psi TRANSDUCER T4 4 T3 4 U10 GRND RETURN TEMP LOOP 1 0 5 VDC THERMISTOR 0V U9 CW INLET TEMPERATURE 0 5 VDC THE...

Страница 33: ...d Acorn is notified in writing within one year from date of shipment F O B Industry California This warranty does not cover installation or labor charges and does not apply to materials which have bee...

Страница 34: ...ACORN CON TROLS ACORN CON TROLVALVES COM 1 8 0 0 4 8 8 8 9 9 9 34 NOTES...

Страница 35: ...ACO RN CON TROLS ACORN CON TROLVALVES COM 1 8 0 0 4 8 8 8 9 9 9 35 NOTES...

Страница 36: ...00 acorncontrolvalves com 1 16 19 L1T00016 15125 Proctor Avenue City of Industry CA 91746 USA P 800 488 8999 P 626 336 4561 F 626 961 2200 www acorncontrolvalves com Font used BEBAS NEUE MORRIS INTERN...

Отзывы: