c. An incorrect refrigerant charge, restriction or defective compressor (not pumping) will also

 cause the compressor to run without producing cold water. All these signs indicate a
 problem within the refrigeration system and the water cooler must be checked by an
 authorized service company.

4. Compressor Cycling On Overload Protector 

a. A dirty condenser or a blocked fan will cause a high head pressure and frequent cycling of

 the overload protector. 

b. Check the incoming voltage to make sure it is within 10% of the serial nameplate rating. 
c. A restriction or moisture in the system will also cause intermittent cycling. A certified

 refrigeration mechanic should be contacted in this situation.

d. Change the overload or relay if defective.

5. Noisy Operation 

a. Check to make sure the fan blade is rotating freely. 
b. Make sure the water cooler is correctly mounted to the wall. Absence of the two lower

 mounting bolts may cause excess noise and vibration. 

c. Check the compressor mounting to make sure the pins and clips are not rattling. If the

 compressor appears to be noisy internally, it must be replaced. 

6. Restricted Or No Water Flow 

a. Ensure water supply service stop valve is fully open. 
b. Verify minimum 20 psig supply line flow pressure. 
c. Check for twists or kinks in bubbler tubing. 
d. Check the water inlet strainer. Sediment from the main supply can get trapped in the

 screen along with installation materials such as pipe dope and flux. The screen should
 be cleaned and checked on a regular basis and replace if needed.
 

NOTE: STRAINER SCREEN MUST BE IN PLACE FOR WATER TO FLOW.

e. The cartridge valve located in the water control assembly or bubbler can also become

 clogged with foreign material. The cartridge valve can only be replaced and not repaired.

f. Check flow adjustment. See start up note #3. 
g. The water cooler may also develop a freezing condition in which the water will become

 frozen inside the evaporator coil. This indicates a refrigeration problem or thermostat
 failure in which case the water cooler needs to be checked by a qualified technician.

CLEANING & MAINTENANCE GUIDE:

1. Motors have lifetime lubrication and do not require scheduled maintenance.

2. Excess dirt or poor ventilation will cause the compress` more frequently. 

3. Periodically remove access panels and clean out in-line strainer.

4. Do NOT use harsh chemicals, abrasive or petroleum based cleaners. Use of these will void the 

Acorn warranty.

5. Exterior panels can be cleaned using mild household detergents or warm, soapy water. Extra  care 

must be used cleaning chrome plated items and mirror finished stainless steel. They can scratch 
easily and should only be cleaned using a clean, soft cloth and mild soap with water or a mild glass 
cleaner.

ACORN ENGINEERING FIELD SERVICE

TOLL FREE

 800-743-8259 • 

LOCAL

  626-855-4866 • 

FAX

 626-855-4863

7020-905-001

Page 6 of 11

Date: 08/11/14

Please visit 

 

for most current specifications.

www.acorndrinkingfountains.com

 

INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

Содержание A172.8UBL Series

Страница 1: ...ed by other causes such as mishandling or improper care or abnormal use The repair or replacement of the defective materials shall constitute the sole remedy of the Buyer and the sole remedy of Acorn...

Страница 2: ...nt ROUGHING IN AND DIMENSIONAL DRAWING Prior to roughing consult with local state and federal codes for proper mounting height A172 8UBL SERIES REFRIGERATED BI LEVEL WALL MOUNTED WATER COOLER Note the...

Страница 3: ...ng current Acorn Engineering installation instructions and if components are assembled to the fixture that is not approved by Acorn Engineering 10 Fixture operates within water pressure range of 20 to...

Страница 4: ...rackets ensuring the bracket tabs engage AND seat in the slots in the back of the water coolers NOTE Hanging of refrigerated unit first is recommended since it is the heavier of the two Verify water c...

Страница 5: ...d screwdriver and turning clockwise to make colder and counterclockwise to make warmer c Bubbler Stream Bubbler can be rotated slightly to direct the stream backwards or forwards Adjust the stream to...

Страница 6: ...with installation materials such as pipe dope and flux The screen should be cleaned and checked on a regular basis and replace if needed NOTE STRAINER SCREEN MUST BE IN PLACE FOR WATER TO FLOW e The c...

Страница 7: ...on the cartridge with the ports in the valve body NOTE STRAINER SCREEN MUST BE IN PLACE FOR WATER TO FLOW CARTRIDGE VALVE PARTS BREAKDOWN ACORN ENGINEERING FIELD SERVICE TOLL FREE 800 743 8259 LOCAL...

Страница 8: ...nsure that the water line is depressurized Push collet square towards the push in fitting body and hold While holding the collet in pull on the PE tubing to remove from the push in fitting TO CUT TUBE...

Страница 9: ...t Strainer Plug Removal of P E Tubing from Push in Fittings 32 NOTE 29 Flow Restrictor Only Available With Low Flow Bubbler 1 2 3 11 5 6 5 9 4 8 8 7 10 12 13 16 14 15 27 27 24 17 17 16 15 34 25 26 23...

Страница 10: ...15 34 25 26 23 22 21 19 18 20 33 15 16 15 29 28 31 30 32 28 29 34 38 39 41 40 39 37 38 35 36 38 43 42 39 44 11 15 16 15 NOTE 29 Flow Restrictor Only Available With Low Flow Bubbler Universal Maintenan...

Страница 11: ...7012 062 001 FAN MOTOR 220V 19 7003 350 000 FAN BLADE 20 7003 201 000 CONDENSER 7012 801 000 COMPRESSOR 7012 030 001 COMPRESSOR 220V 7012 802 000 START RELAY 7012 031 000 START RELAY 220V 7012 803 00...

Отзывы: