B5C Operation And Maintenance Manual 

85950-301-000 RA 

 

Aug. 05, 2016 

17

3.7  Menu “4_OUT TEST” 

During system installation and testing, it may be necessary to force relays and buzzers on 
and off.  

The  Relay  Testing  feature  allows  the  user  to  force  the  actuation  of  each  relay.  This 
function  forces  an  Actuate  vs.  De-actuate  action,  not  an  energized  vs.  non-energized 
action.  Therefore  the  user  must  be  aware  of  these  relays,  which  have  been  defined  as 
normally energized or not normally energized.  

The 4mA (1VDC/2VDC) and 20mA (5VDC/10VDC) outputs can be tested too. 

Up

F2

RETURN

TO MAIN MENU

   MENU: TESTING:

  1. TEST RELAY1

   PRE        NEXT       ENTER

   1. TEST RELAY1

   OFF

    ON           OFF          EXIT

F3

F3

F1

F2

   1. TEST RELAY1

   ON

    ON           OFF          EXIT

Up

   MENU: TESTING:

  2. TEST RELAY2

   PRE        NEXT       ENTER

   2. TEST RELAY2

   OFF

    ON           OFF          EXIT

F3

F3

F1

F2

   2. TEST RELAY2

   ON

    ON           OFF          EXIT

F1

Up

F2

   MENU: TESTING:

  3. TEST RELAY3

   PRE        NEXT       ENTER

   3. TEST RELAY3

   OFF

    ON           OFF          EXIT

F3

F3

F1

F2

   3. TEST RELAY3

   ON

    ON           OFF          EXIT

Up

   MENU: TESTING:

  4. TEST BUZZER

   PRE        NEXT       ENTER

   4.TEST BUZZER

   OFF

    ON           OFF          EXIT

F3

F3

F1

F2

   4.TEST BUZZER

   ON

    ON           OFF          EXIT

F1

F2

F1

Up

F2

   MENU: TESTING:

  5. TEST 4MA

   PRE        NEXT       ENTER

   5. TEST 4MA

   OFF

    ON           OFF          EXIT

F3

F3

F1

F2

   5. TEST 4MA

   ON

    ON           OFF          EXIT

Up

   MENU: TESTING:

  6. TEST 20MA

   PRE        NEXT       ENTER

   6.TEST 20MA

   OFF

    ON           OFF          EXIT

F3

F3

F1

F2

   6.TEST 20MA

   ON

    ON           OFF          EXIT

F1

F2

F1

   MENU: TESTING:

  EXIT TESTING

   PRE        NEXT       ENTER

F2

F1

F2

F1

VDC OUTPUT CAN BE TESTED AT THE SAME TIME AS
TESTING 4/20MA:
WHEN OUTPUT 4MA, THE VDC OUTPUTS 1V OR 2V
WHEN OUTPUT 20MA THE VDC OUTPUTS 5V OR 10V
4mA and 20mA TEST ONLY IN Q5

 

Содержание B5C

Страница 1: ...B5C GAS TRANSMITTER SENSOR INSTALLATION OPERATION AND MAINTENANCE MANUAL AUTOMATION COMPONENTS INC 2305 PLEASANT VIEW ROAD MIDDLETON WI 53562 PHONE 888 967 5224 FAX 608 831 7407 Web workaci com...

Страница 2: ...enu 10 3 2 2 Hush Buzzer and Relay 10 3 2 3 Reset Latched Hushed 10 3 2 4 Reset MENU Password 10 3 2 5 Exit Tool Mode 10 3 3 MAIN MENU TREE 11 3 4 MENU 1_SYSTEM SETUP 12 3 4 1 System Settings 12 3 5 M...

Страница 3: ...s Alarm Input On Concentration Off Concentration Output Trigger Alarm1 Instant 25ppm 20ppm Relay1 Alarm2 Instant 50ppm 40ppm Relay1 Relay2 Alarm3 Instant 100ppm 95ppm Relay1 2 3 Buzzer1 Alarm4 Fault 2...

Страница 4: ...master nodes are allowed to send and receive tokens on the MSTP network Passive slave nodes on the other hand may only transmit data frames on the network in response to a request from a master node P...

Страница 5: ...1 F2 F3 Relays 3 Relays SPDT Dry contacts 1 0A maximum at 30 VDC resistive load 0 3A maximum at 125VAC resistive load Buzzer 55 dB at 10 feet 2700 Hz Buzzer 1 2 3 Programmable tone Tone chirp once chi...

Страница 6: ...read out placing it at about eye level is strong recommended The location should be accessible for the purposes of routine re calibration and periodic sensor replacement Sufficient room should be left...

Страница 7: ...he output signal 2 3 Terminals B5C Terminals 2 3 1 Wire and Cable Terminal blocks TB1 to TB7 accept 12 AWG to 24 AWG wire Use 16 AWG or 18 AWG wire for the power supply in long wiring runs which can b...

Страница 8: ...and it is chosen using a jumper at J4 J4 1 2 Terminator Disabled OFF default J4 2 3 Terminator Enabled ON 2 3 3 RS 485 Driver Replacement RS 485 lines in heavy industrial environments are sometimes su...

Страница 9: ...he same AC source Use extreme caution when sharing a common AC source Sharing a common DC source is less problematic When the B5C input power is AC the 24VAC can be either grounded or non grounded Pol...

Страница 10: ...One is RX LED which indicates the data stream received in from the controller The other is TX LED which indicates the data stream out of the B5C Note If the TX LED or the RX LED is always ON is indica...

Страница 11: ...to browse next item of the current menu Press key F3 to enter the main menu for more configuration and settings 3 2 2 Hush Buzzer and Relay Press key F3 to silence the buzzer and buzzer style relays...

Страница 12: ...E NEXT ENTER F3 F1 F2 F3 F3 F3 F3 F1 F1 F1 F1 F2 F2 F2 F2 F2 F2 F1 F3 F3 F1 F2 F1 F3 F2 F1 F1 F1 F3 MENU 3_ SPAN CAL PRE NEXT ENTER MENU 4_ OUTPUT TEST PRE NEXT ENTER MENU 6_ ALARM SETUP PRE NEXT ENTE...

Страница 13: ...ight The LCD backlight can be set to Always Off Always On and Auto Power Saving mode In Auto Power Saving mode the backlight will turn on for 10 seconds after any key has been pressed Default setting...

Страница 14: ...Calibration mode so that the lowest reading goes to zero When AutoZero is set to OFF the unit will not adjust its own zero and work off the last manual or factory calibration Default value is OFF NOT...

Страница 15: ...ult is 21 Check Battery The sensor board is equipped with a coin battery This setting will enable or disable the B5C to check the battery voltage and beep for a low battery level Default is ON Output...

Страница 16: ...Press key F3 and the device will show the calibration notice and then ask if you want to continue The middle line will display the current concentration Apply the Zero Gas Wait for about 3 minutes or...

Страница 17: ...ontinue The middle line will display the current concentration Apply the calibration gas Wait for about 3 minutes or until the reading is stable Press key F3 to confirm SPAN CAL When the device is in...

Страница 18: ...F2 1 TEST RELAY1 ON ON OFF EXIT Up MENU TESTING 2 TEST RELAY2 PRE NEXT ENTER 2 TEST RELAY2 OFF ON OFF EXIT F3 F3 F1 F2 2 TEST RELAY2 ON ON OFF EXIT F1 Up F2 MENU TESTING 3 TEST RELAY3 PRE NEXT ENTER...

Страница 19: ...VIEW A OUT SETUP PRE NEXT ENTER 5 VIEW EVENT RECORDS PRE NEXT ENTER 6 VIEW SETTING EXIT PRE NEXT ENTER F2 F1 F1 F1 F1 F1 F1 VIEW RELAY 1 EXIT NEXT ENTER 1 DE ENERGIZE 2 NON LATCHING 3 NORMAL STYLE KE...

Страница 20: ...ntaneous gas reading 15 MIN AVG STEL Short Term Exposure Limit average reading over 15 minutes 8 HOURS AVG TWA 8 hour Time Weighted Average average reading over 8 hours DAILY PEAK daily peak reading F...

Страница 21: ...Latching ON Delay Delay on Actuation or Delay on Make For each relay a separate time delay may be set from 0 to 990 seconds before an alarm condition will cause the relay to actuate Default is 5 secon...

Страница 22: ...sed to assist in testing the installation before commissioning When simulation is enabled the unit will not detect gas concentrations it will display the simulated value and use it to calculate the st...

Страница 23: ...eplace the entire smart sensor assembly complete the following steps 1 Power down the transmitter 2 Remove the four screws securing the enclosure lid assembly to the base enclosure and remove the encl...

Страница 24: ...ent Parts Code Gas Symbol Span Smart Sensor Assembly 1 Carbon Monoxide CO 0 250ppm 85930 018 001 2 Carbon Monoxide CO 0 1000ppm 85930 018 201 4 1 4 Accessories Pump thru Splash Guard Kit Calibration C...

Страница 25: ...roblem RS 485 driver U6 is damaged Controller side RS 485 driver has problem Disconnect the cable to isolate the problem Replace U6 IC on main board Replace the RS 485 driver on the controller No resp...

Страница 26: ...reading all manuals ACI shall not be responsible for any liability arising from auxiliary interfaced equipment nor any damage resulting from the installation or operation of this equipment ACI s tota...

Отзывы: