background image

B5C Operation And Maintenance Manual 

85950-301-000 RA 

 

Aug. 05, 2016 

8

2.3.5

 

Note for B5C: 

The  B5C  supports  BACnet  MS/TP  protocol  and  can  be  networked  to  form  a  BACnet 
MS/TP network. 

The B5C default baud rate is 38400bps. 

Each B5C on the MS/TP network must have a unique BACnet MAC address and unique 
Device Instance Number (Object ID).  

 

B5C valid MAC addresses are 0-127 for master node, 0-254 for slave node. 

 

B5C default MAC address is 126. 

 

Default Device Instance Number (Object ID) is 4005. 

The B5C power supply and RS-485 connection are similar to the Q5C. The B5C doesn't 
have terminal blocks TB4 and TB6. 

Avoid running communication wires or sensor input wires next to AC power wires or the 
relay output wires. These can be sources of noise that can affect signal quality. 

The B5C has a half wave rectifier on board. You will damage devices if you mix half 
wave  and  full  wave  rectifiers  on  the  same  AC  source.  Use  extreme  caution  when 
sharing a common AC source. Sharing a common DC source is less problematic. 

When the B5C input power is AC, the 24VAC can be either grounded or non-grounded. 
Polarization is very important when the B5C is connected to a network.  Make sure the 
Neutral is connected to the GND of TB5. 

2.3.6

 

Certification: 

 
The Q5/B5 series have been certified to the following Standard: 

Safety requirement for Electrical Equipment for Measurement, Control, and Laboratory Use- 
Part 1:  General Requirements CAN/CSA-22.2 No.  61010-1 Third Edition, Dated May 11, 2012;  
And 
Safety Requirements for Electrical Equipment for measurement, Control, and Laboratory Use- 
Part 1:  General Requirements UL 61010-1 Third Edition, Dated May 11, 2012. 

Installation must be in accordance with ANSI/NFPA 70, National Electrical Code (NEC); 
the 
Canadian Electrical Code (CEC), Part I, CSA C22.1, and CSA C22.2 No. 0; and the 
Manufacturers’ installation instructions 

 

The Q5C/B5C Carbon Monoxide transmitters are certified to UL2075 Life Safety 
Standards. Project#: G102400708, G102389154. For details, contact ACI. 

Содержание B5C

Страница 1: ...B5C GAS TRANSMITTER SENSOR INSTALLATION OPERATION AND MAINTENANCE MANUAL AUTOMATION COMPONENTS INC 2305 PLEASANT VIEW ROAD MIDDLETON WI 53562 PHONE 888 967 5224 FAX 608 831 7407 Web workaci com...

Страница 2: ...enu 10 3 2 2 Hush Buzzer and Relay 10 3 2 3 Reset Latched Hushed 10 3 2 4 Reset MENU Password 10 3 2 5 Exit Tool Mode 10 3 3 MAIN MENU TREE 11 3 4 MENU 1_SYSTEM SETUP 12 3 4 1 System Settings 12 3 5 M...

Страница 3: ...s Alarm Input On Concentration Off Concentration Output Trigger Alarm1 Instant 25ppm 20ppm Relay1 Alarm2 Instant 50ppm 40ppm Relay1 Relay2 Alarm3 Instant 100ppm 95ppm Relay1 2 3 Buzzer1 Alarm4 Fault 2...

Страница 4: ...master nodes are allowed to send and receive tokens on the MSTP network Passive slave nodes on the other hand may only transmit data frames on the network in response to a request from a master node P...

Страница 5: ...1 F2 F3 Relays 3 Relays SPDT Dry contacts 1 0A maximum at 30 VDC resistive load 0 3A maximum at 125VAC resistive load Buzzer 55 dB at 10 feet 2700 Hz Buzzer 1 2 3 Programmable tone Tone chirp once chi...

Страница 6: ...read out placing it at about eye level is strong recommended The location should be accessible for the purposes of routine re calibration and periodic sensor replacement Sufficient room should be left...

Страница 7: ...he output signal 2 3 Terminals B5C Terminals 2 3 1 Wire and Cable Terminal blocks TB1 to TB7 accept 12 AWG to 24 AWG wire Use 16 AWG or 18 AWG wire for the power supply in long wiring runs which can b...

Страница 8: ...and it is chosen using a jumper at J4 J4 1 2 Terminator Disabled OFF default J4 2 3 Terminator Enabled ON 2 3 3 RS 485 Driver Replacement RS 485 lines in heavy industrial environments are sometimes su...

Страница 9: ...he same AC source Use extreme caution when sharing a common AC source Sharing a common DC source is less problematic When the B5C input power is AC the 24VAC can be either grounded or non grounded Pol...

Страница 10: ...One is RX LED which indicates the data stream received in from the controller The other is TX LED which indicates the data stream out of the B5C Note If the TX LED or the RX LED is always ON is indica...

Страница 11: ...to browse next item of the current menu Press key F3 to enter the main menu for more configuration and settings 3 2 2 Hush Buzzer and Relay Press key F3 to silence the buzzer and buzzer style relays...

Страница 12: ...E NEXT ENTER F3 F1 F2 F3 F3 F3 F3 F1 F1 F1 F1 F2 F2 F2 F2 F2 F2 F1 F3 F3 F1 F2 F1 F3 F2 F1 F1 F1 F3 MENU 3_ SPAN CAL PRE NEXT ENTER MENU 4_ OUTPUT TEST PRE NEXT ENTER MENU 6_ ALARM SETUP PRE NEXT ENTE...

Страница 13: ...ight The LCD backlight can be set to Always Off Always On and Auto Power Saving mode In Auto Power Saving mode the backlight will turn on for 10 seconds after any key has been pressed Default setting...

Страница 14: ...Calibration mode so that the lowest reading goes to zero When AutoZero is set to OFF the unit will not adjust its own zero and work off the last manual or factory calibration Default value is OFF NOT...

Страница 15: ...ult is 21 Check Battery The sensor board is equipped with a coin battery This setting will enable or disable the B5C to check the battery voltage and beep for a low battery level Default is ON Output...

Страница 16: ...Press key F3 and the device will show the calibration notice and then ask if you want to continue The middle line will display the current concentration Apply the Zero Gas Wait for about 3 minutes or...

Страница 17: ...ontinue The middle line will display the current concentration Apply the calibration gas Wait for about 3 minutes or until the reading is stable Press key F3 to confirm SPAN CAL When the device is in...

Страница 18: ...F2 1 TEST RELAY1 ON ON OFF EXIT Up MENU TESTING 2 TEST RELAY2 PRE NEXT ENTER 2 TEST RELAY2 OFF ON OFF EXIT F3 F3 F1 F2 2 TEST RELAY2 ON ON OFF EXIT F1 Up F2 MENU TESTING 3 TEST RELAY3 PRE NEXT ENTER...

Страница 19: ...VIEW A OUT SETUP PRE NEXT ENTER 5 VIEW EVENT RECORDS PRE NEXT ENTER 6 VIEW SETTING EXIT PRE NEXT ENTER F2 F1 F1 F1 F1 F1 F1 VIEW RELAY 1 EXIT NEXT ENTER 1 DE ENERGIZE 2 NON LATCHING 3 NORMAL STYLE KE...

Страница 20: ...ntaneous gas reading 15 MIN AVG STEL Short Term Exposure Limit average reading over 15 minutes 8 HOURS AVG TWA 8 hour Time Weighted Average average reading over 8 hours DAILY PEAK daily peak reading F...

Страница 21: ...Latching ON Delay Delay on Actuation or Delay on Make For each relay a separate time delay may be set from 0 to 990 seconds before an alarm condition will cause the relay to actuate Default is 5 secon...

Страница 22: ...sed to assist in testing the installation before commissioning When simulation is enabled the unit will not detect gas concentrations it will display the simulated value and use it to calculate the st...

Страница 23: ...eplace the entire smart sensor assembly complete the following steps 1 Power down the transmitter 2 Remove the four screws securing the enclosure lid assembly to the base enclosure and remove the encl...

Страница 24: ...ent Parts Code Gas Symbol Span Smart Sensor Assembly 1 Carbon Monoxide CO 0 250ppm 85930 018 001 2 Carbon Monoxide CO 0 1000ppm 85930 018 201 4 1 4 Accessories Pump thru Splash Guard Kit Calibration C...

Страница 25: ...roblem RS 485 driver U6 is damaged Controller side RS 485 driver has problem Disconnect the cable to isolate the problem Replace U6 IC on main board Replace the RS 485 driver on the controller No resp...

Страница 26: ...reading all manuals ACI shall not be responsible for any liability arising from auxiliary interfaced equipment nor any damage resulting from the installation or operation of this equipment ACI s tota...

Отзывы: