B5C Operation And Maintenance Manual
85950-301-000 RA
Aug. 05, 2016
14
The B5C supports the execution of the TimeSynchronization service and
UTCTimeSynchronization service. The clock can be adjusted remotely.
ADJ
Contrast:
Adjust the LCD contrast. Valid values are between 10 (light) and 50 (dark).
Default is 21.
Check
Battery
The sensor board is equipped with a coin battery. This setting will enable or
disable the B5C to check the battery voltage and beep for a low battery
level.
Default is ON.
Output
Priority:
Alarm output (BV) present_value and relay output (BO) present_value
support command prioritization. The B5C has priority #12 as default.
The lower the priority umber the more critical the nature of the output.
Priority #1 is considered the highest priority. Priority #16 is the lowest
priority.