B5C Operation And Maintenance Manual
85950-301-000 RA
Aug. 05, 2016
12
3.4 Menu “1_SYSTEM SETUP”
The system setup subdivision contains general settings for monitor operations,
communications and 4-20mA calibrations.
3.4.1
System Settings
Password:
Default password is 4321.
MAC
Address:
The B5C RS-485 address can be defined from 0 to 255. B5C default address
is 126.
Object ID:
BACnet Device Instance Number. Default is 4005.
Baud rate:
Define baud rate for RS-485 communication with BACnet protocol.
B5C default baud rate is 38400 bps.
Scroll Rate:
In normal operation, the sensor and relay status information scrolls
automatically. Set the number of seconds for each item to be displayed.
Default value is 3 seconds.
Backlight:
The LCD backlight can be set to Always Off, Always On and Auto Power
Saving mode. In Auto Power Saving mode, the backlight will turn on for 10
seconds after any key has been pressed. Default setting is Auto.
UTC Offset
The B5C supports the execution of the TimeSynchronization service and
UTCTimeSynchronization service. It indicates the number of minutes ( -
780 to +780) offset between local standard time and Universal Time
Coordinated. Default is +300 (US & Canada Eastern Time).
Daylight
Saving
It indicates whether daylight saving time is in effect (Enabled) or not
(Disabled) at the B5C location in UTCTimeSynchronization service.
Default is Enabled.
New
Password:
The new password can be any combination of up to four digits. Default
password is 4321.
Warning:
Be sure that you record the new password in a safe and
secure location!
Protocol:
The B5C supports BACnet MS/TP master or slave protocol. Default is
MS/TP master.