Installation & Operation Manual - Model AV3000
Contents of this Manual are Subject to Change Without Notification
Page 15
8.4 Fume Hood Controller Configuration
Standard calibration constants for the FVC “VorTek Direct” input have been derived for each AV3000 transmitter range. Using the
FVC2000 Configuration Tool, set the three VorTek parameters as show below for the given size valve.
FVC2000 Config.
Tool Parameter
AV3100-06
AV3100-08
AV3100-10
AV3100-12
AV3100-14
AV3200-18
AV3200-24
AV3200-36
AV3200-48
0 - 330 CFM
0 - 561 CMH
0 - 850 CFM
0 - 1444 CMH
0 - 1370 CFM
0 - 2378 CMH
0 - 1900 CFM
0 - 3228 CMH
0 - 3000 CFM
0 - 5097 CMH
0 - 3400 CFM
0 - 5777 CMH
0 - 4200 CFM
0 - 7136 CMH
0 - 6800 CFM
0-11553 CMH
0 - 8400 CFM
0-14272 CMH
Vortek
Span FPM
185
178
130
111
161
118
154
118
118
Coef
Bias FPM
56
56
56
56
56
56
56
56
56
Vortek
Area
Sq. F
0.20
0.50
0.50
0.5
1.00
1.00
2.00
2.00
2.5
Vortek
Input
Channel
08
08
08
08
08
08
08
08
08
After these
parameters are saved to the FVC Controller, the “VorTek Direct” input will provide the properly scaled CFM value for
the AV3000 transmitter to which it is connected. If it is necessary to adjust the airflow calibration in the field, the
Vortek Coef
Span FPM
parameter can be modified.
8.5 SmartLab Controller Configuration
Standard calibration constants for the SLC “VorTek Direct” input have been derived for each AV3000 transmitter range. Using the
SmartLab Configuration Software, set the “VorTek Direct” input parameters as show below for the given size valve.
Function Name:
AV3100-06
AV3100-08
AV3100-10
AV3100-12
AV3100-14
AV3200-18
AV3200-24
AV3200-36
AV3200-48
Input, Vortek Direct
0
– 330 CFM
0
– 561 CMH
0
– 850 CFM
0
– 1444 CMH
0
– 1370 CFM
0
– 2378 CMH
0 - 1900 CFM
0 - 3228 CMH
0 - 3000 CFM
0 - 5097 CMH
0 - 3400 CFM
0 - 5777 CMH
0 - 4200 CFM
0 - 7136 CMH
0 - 6800 CFM
0-11553 CMH
0 - 8400 CFM
0-14272 CMH
Sensor Sel:
1x1
1x1
1x1
1x1
1x1
1x1
1x1
1x1
1x1
Threshold:
(Hz)
50
50
50
50
50
50
50
50
50
Cal Bias:
(Hz)
58
58
58
58
58
58
58
58
58
Cal Span:
(Hz)
680
316
220
173
134
123
111
90.5
84.5
Duct
(sq ft)
1
1
1
1
1
1
1
1
1
After these parameters are saved to the SmartLab Controller, the “VorTek Direct” input will provide the properly scaled CFM value
for the AV3000 transmitter to which it is connected. If it is necessary to adjust the airflow calibration in the field, the
Cal Span
parameter can be modified.