8.3 AV3000 Transmitter Configuration
In order for the AV3000 Transmitter to
operate properly with the “AccuValve
®
Direct
Input Board” the transmitter output jumpers must be configured for 2-10 v operation and
the Transmitter Full-Scale Range must remain set to the factory default values as
shown below.
Valve Model
Transmitter
Full Scale @ 10 v
CFM
CMH
AV3100-06
330
561
AV3100-08
850
1444
AV3100-10
1370
2328
AV3100-12
1900
3228
AV3100-14
3000
5097
AV3200-18
3400
5777
AV3200-24
4200
7136
AV3200-36
6800
11553
AV3200-48
8400
14272