Installation & Operation Manual - Model AV3000
Contents of this Manual are Subject to Change Without Notification
Page 10
6.3 Field Wiring Schematics
The following diagrams are intended to be used as examples for connecting the
AccuValve
®
AV3000 to Field Devices. Reference the inside of transmitter cover for
identification of connectors.
NOTE: Use 16-22 AWG Shielded Cable.
6.3.1Typical wiring between the AccuValve
®
and DDC Control Panel
Wiring shown is for (2-10 VDC or 0-10 VDC) Analog Output. For using a current Analog Output (4-20mA or 0-20mA) install a
500-ohm 1/4 watt resistor across Analog and - terminals at the Controller.
1
Polarity must be maintained if transformer is used to power multiple devices otherwise equipment may be damaged. Power
source must include a circuit breaker and be current limited to 8 amps maximum and grounded on the (-) side.
2
3. The above wiring diagrams are intended to be used as a general guide for wiring the AV3000 to a DDC Controller. The
detailed wiring diagrams provided by the Controls Contractor shall be used in conjunction with this document.
Actuator #2 is used for 12x36" and 12x48" valves only.
4
6.3.2 Typical wiring between AccuValve
®
and Tek-Air Fume Hood Controller.
Tek-Air FVC Controller
I / P Out +
I / P Out
-
24 VAC
Black (Power/Signal Common)
Red (+ 24V Power Input)
White (Ctrl. Signal In, 2 to 10V)
Actuator
X4 Pin 2 (Common)
X4 Pin 1 (+ Power Input)
X2 Pin 1 (+ Output Signal, 2-10v)
X2 Pin 2 (Common)
Transmitter
HOT
Common
Notes:
1. Power Requirements: Transmitter (2.5VA), Actuator (23VA), FVC Controller (10VA)
2. 24 VAC source must include circuit breaker and be current limited to 8 amps maximum and be grounded on the (-) side.
3. Polarity must be maintained if transformer is used to power multiple devices otherwise equipment damage may result.
24 VAC
Transformer
Line
Volts
AccuValve Direct
Input Board
Signal (2-10)
+ Power (15v)
Common
Cable Shown Below
20 AWG 3-Conductor
Shielded Plenum
(Windy City Wire #003330)
AccuValve, Model AV3000
500-ohm 1/4w
RED
WHITE
BLACK
RED
WHITE
BLACK
DDC Ctrl. Panel
Analog
Analog Output -
Transformer
Line
Volts
24 VAC
X4 (2) Common
X4 (1) + 24V Pwr.
X2 (1) Output Sig.
X2 (2) Common
Transmitter
Analog Input +
Analog Input -
HOT
COM.
AV3000
2
1
(Black) Common
(Red) + 24V Pwr.
(White) Ctrl. Sig.
Actuator
(Black) Common
(Red) + 24V Pwr.
(White) Ctrl. Sig.
Actuator #2
4
DDC Ctrl. Panel
Analog
Analog Output -
Transformer
Line
Volts
24 VAC
X4 (2) Common
X4 (1) + 24V Pwr.
X2 (1) Output Sig.
X2 (2) Common
Transmitter
Analog Input +
Analog Input -
HOT
COM.
AV3000
1
2
(Black) Common
(Red) + 24V Pwr.
(White) Ctrl. Sig.
Actuator
(Black) Common
(Red) + 24V Pwr.
(White) Ctrl. Sig.
Actuator #2
4
Controller with Common I/O & Power Ground