Installation & Operation Manual - Model AV3000 

Contents of this Manual are Subject to Change Without Notification 

Page 11 

 

6.3.3 Typical wiring between AccuValve

®

 and Tek-Air SmartLab Controller 

equipped with the AccuValve

®

 Direct Input board. 

 

Tek-Air SLC Controller

AO +

AO 

24 VAC

Black  (Power/Signal Common)

Red (+ 24V Power Input)

White (Ctrl. Signal In, 2 to 10V)

Actuator

X4 Pin 2 (Common)

X4 Pin 1 (+ Power Input)

X2 Pin 1 (+ Output Signal, 2-10v)

X2 Pin 2 (Common)

Transmitter

HOT

Common

Notes:

1. Power Requirements: Transmitter (2.5VA), Actuator (23VA), SLC Controller (16VA)
2. Polarity must be maintained if transformer is used to power multiple devices otherwise equipment may be damaged.
3. 24 VAC source must include circuit breaker and be current limited to 8 amps maximum and be grounded on the (-) side.
4. Actuator Control Signal pictured above is for 2-10 VDC Analog Output.  For controlling the actuator with a 4-20mA Analog 
Output install a 500-ohm ¼ watt resistor across Analog Output terminals at the controller.

24 VAC 

Transformer

Line 

Volts

AccuValve Direct 

Input Board

Signal (2-10)

+ Power (15v)

Common

Cable Shown Below:

20 AWG 3-Conductor

Shielded Plenum

(Windy City Wire #003330)

AccuValve, Model AV3000

RED

WHITE

BLACK

RED

WHITE

BLACK

 

 
6.3.4 Typical wiring between AccuValve

®

 and Tek-Air SmartLab Controller using 

the SmartLab’s Powered Analog Input (AI-3 or AI-4). 

 

Tek-Air SLC Controller

AO +

AO 

24 VAC

Black  (Power/Signal Common)

Red (+ 24V Power Input)

White (Ctrl. Signal In, 2 to 10V)

Actuator

X4 Pin 2 (Common)

X4 Pin 1 (+ Power Input)

X2 Pin 1 (+ Output Signal, 4-20mA)

X2 Pin 2 (Common)

Transmitter

HOT

Common

Notes:

1. Power Requirements: Transmitter (2.5VA), Actuator (23VA), SLC Controller (16VA).
2. Polarity must be maintained if transformer is used to power multiple devices otherwise equipment may be damaged.
3. 24 VAC source must include circuit breaker and be current limited to 8 amps maximum and be grounded on the (-) side.
4. Actuator Control Signal pictured above is for 2-10 VDC Analog Output.  For controlling the actuator with a 4-20mA Analog 
Output install a 500-ohm 1/4 watt resistor across Analog Output terminals at the controller.

24 VAC 

Transformer

Line 

Volts

AI-4 IN 

+

AI-4 IN V

AI-4 IN 

-

20 AWG 3-Conductor

Shielded Plenum

(Windy City Wire #003330)

AccuValve, Model AV3000

RED

WHITE

BLACK

RED

WHITE

BLACK

 

Содержание AccuValve AV3000

Страница 1: ...of this Manual are Subject to Change Without Notification Airflow Control Valve Patented U S 6 991 177 7 543 759 Manufactured by Accutrol Representative AV3000 MANUAL ACCUTROL JANUARY 2019 ECN 2433 2...

Страница 2: ...s against defects or damages arising from improper installation where installation is by persons other than Manufacturer against defects in products or components not manufactured by Manufacturer or a...

Страница 3: ...NTENTS iii SECTION 1 INTRODUCTION 1 SECTION 2 SPECIFICATIONS 3 SECTION 3 MODEL CODE DESCRIPTION 4 SECTION 4 PHYSICAL DIMENSIONS WEIGHTS 5 SECTION 5 INSTALLATION 6 SECTION 6 WIRING 9 SECTION 7 OUTPUT C...

Страница 4: ...and compresses creating a laminar zone optimum for measuring airflow velocity The vortex shedding airflow sensors provide a digital pulse train to the airflow transmitter which is directly proportiona...

Страница 5: ...3 2 AV3200 36 and 48 Dual Valves Airflow Transmitter Actuator 1 Electric Actuator Access Cover Drive Shaft Airflow Transmitter Housing Actuator 2 Mounting Supports Valve 2 Valve 1 Airflow Inlet View...

Страница 6: ...ax differential pressure across valve ENVIRONMENTAL Temperature Air stream 20 to 140 deg F Ambient 25 to 125 deg F Humidity 0 to 95 RH non condensing TRANSMITTER ELECTRICAL Input Power 24 VAC 20 50 60...

Страница 7: ...10v Belimo NMQB24 MFT B FLP 4 Fail Open Closed 0 10v Belimo NKQ24 MFT A FSP 5 Fail Open Closed 2 10v Belimo NKQ24 MFT B FSP SIZE 06 6 Diameter 08 8 Diameter 10 10 Diameter 12 12 Diameter 14 14 Diamete...

Страница 8: ...6 7 3 AV3100 10 9 88 250 24 610 15 381 20 9 1 AV3100 12 11 88 300 27 686 17 432 26 11 8 AV3100 14 13 88 350 30 762 19 483 30 13 6 4 2 Rectangular Sizes Valve Model W L H Weight in mm in mm in mm lbs k...

Страница 9: ...and valve access cover 5 To support the weight of the valve install duct hangers within 12 inches 305 mm of valve connections NOTE Reference Section 4 for valve weights 6 After the duct section is pr...

Страница 10: ...Change Without Notification Page 7 Round Valve Installation Standard Slip Fit Valve Using Draw Band Round Valve Installation Option F Flanges 3 8 bolts lock washers and nuts 14 356mm Minimum Clearanc...

Страница 11: ...ts 14 356mm Minimum Clearance Rectangular Valve Installation Option F Flanges Additional Requirements for Installing 12X36 and 12x48 Valves All dual valves 12x36 and 12x48 are provided with an integra...

Страница 12: ...a 875 22 2mm conduit fitting 6 1 3 Land the wires to the appropriate terminals secure screws and reinstall plugs NOTE Reference job specific wiring diagrams for details of connections to field devices...

Страница 13: ...troller Tek Air FVC Controller I P Out I P Out 24 VAC Black Power Signal Common Red 24V Power Input White Ctrl Signal In 2 to 10V Actuator X4 Pin 2 Common X4 Pin 1 Power Input X2 Pin 1 Output Signal 2...

Страница 14: ...irect Input Board Signal 2 10 Power 15v Common Cable Shown Below 20 AWG 3 Conductor Shielded Plenum Windy City Wire 003330 AccuValve Model AV3000 RED WHITE BLACK RED WHITE BLACK 6 3 4 Typical wiring b...

Страница 15: ...has been configured to provide either Voltage 0 10v or 2 10v or Current 0 20mA or 4 20mA by using Jumpers JP1 and JP4 The factory default transmitter output is 2 10v unless specified otherwise at the...

Страница 16: ...Fume Hood Controller Applications All FVC2000 applications utilizing the AV3000 must use the AccuValve Direct input board to connect the AV3000 to the FVC controller If the Fume Hood Controller does n...

Страница 17: ...cuValve Direct Input Board the transmitter output jumpers must be configured for 2 10 v operation and the Transmitter Full Scale Range must remain set to the factory default values as shown below Valv...

Страница 18: ...ransmitter to which it is connected If it is necessary to adjust the airflow calibration in the field the Vortek Coef Span FPM parameter can be modified 8 5 SmartLab Controller Configuration Standard...

Страница 19: ...ugh to allow the access door to slide forward CAUTION If the bolt is removed from the captive nut the access cover can spring open possibly causing injury 2 Using two hands squeeze the access cover an...

Страница 20: ...for sheet metal working 1 The access cover is secured to the valve using 12 Tek Screws Remove the 12 Tek Screws using a 5 16 socket and put the screws aside for reinstalling the cover later 2 Remove...

Страница 21: ...Installation Operation Manual Model AV3000 Contents of this Manual are Subject to Change Without Notification A APPENDIX A ACTUATOR TECHNICAL DATA SHEETS...

Страница 22: ...ed Shut off Leakage specification Revised Operating Range Table Revision Date Jan 2012 New Filename AV3000 MANUAL ACCUTROL JAN 2012 Section Description of Change Cover Revised pictures and revised fil...

Отзывы: