14.3 CLIMATIC MANAGEMENT PROCEDURE
PARAMETERS
CF05
ST08
ST03
SD03
SD05
SD07
AR03
AR20
AR21
AR22
AR23
AR25
AR26
AL19
SET POINT FUNCTION
SET-POINT - Configuration PB2
SET-POINT max in PdC
SET-POINT winter (compressor off at outdoor temp. 50 °C)
CLIMATIC SET POINT FUNCTION
Dynamic SET-POINT max increase in heat pump maximum variation
Set External air temp. Dynamic SET-POINT in HP
Dynamic SET-POINT external air temperature differential in heat pump
BOILER FUNCTION (BOILER)
Frost alarm set
Boiler function (heating control)
SET-POINT external air boiler activation (boiler)
Boiler differential (boiler)
Boiler activation delay time (boiler)
SET-POINT external air compressor deactivation
Compressor activation external air differential
PARAMETERS FUNCTIONS ALARMS
Probe for anti-freeze alarm signal
VALUE
4 °C External temperature
65,0 °C max
65,0 °C max
-10,0 °C
-5,0 °C
5,0 °C
4,0 °C - 5,0 °C
0 °C
3,0 °C
0,2 °C
1 (minuti)
0,0 °C
0,5 °C
2,0 °C
14.4 INTEGRATION MANAGEMENT PROCEDURE
PARAMETRI
AR09
AR012
AR15
A16
A17
BOILER FUNCTION (BOILER)
SET-POINT - Antifreeze resistances in heat pump
Heat pump antifreeze heater differential
Adjustment of antifreeze resistances in the heat pump
Thermoregulation of antifreeze heaters in chiller (boiler integration)
Thermoregulation of antifreeze resistances in the heat pump (boiler integration)
VALUE
48,0 °C
2,0 °C
1 (on)
0 (regola si PB1)
0 (regola si PB1)