12
ATTENTION! all electrical connections must be carried
out by qualified personnel and the electrical system must
comply with all applicable regulations
L)
Proceed with the refrigerator connections following all the
instructions given in section 2.3 of this manual. When shaping
the pipes, avoid any type of crushing and make sure that each
portion of the pipe is perfectly thermally insulated from start to
finish.
ATTENTION! compliant with all current regulations.
All refrigeration connections must be carried out by qualified
personnel in possession of the F-GAS certification (DPR
January 27, 2012, n.43)
M)
Once all the connections have been made, request the indoor
unit with the special cover cabinet which must first be placed
from top to bottom on the wall fixing bracket and then rotated
towards the wall until it is hooked onto the special retractable
pins. , placed on the lower fixing plate.
4.4 AIR INTAKE / SMOKE EXHAUST SYSTEM
A modulating high efficiency condensing boiler is located in the
indoor unit of the HUB RADIATOR PACK CF hybrid system.
As regards the discharge of fumes into the atmosphere and the
air intake / fumes exhaust systems, comply with the laws and
regulations in force, which are understood to be fully transcribed
here.
Safety devices are installed on the boiler to control the evacuation
of combustion products.
In the event of a malfunction of the air intake / flue gas exhaust
system, the devices put the boiler in safety and the code E14
flashes on the LCD display.
Tampering with and / or exclusion of these safety devices is
strictly prohibited.
In the event of repeated shutdowns of the boiler, it is necessary
to have the air intake / flue gas exhaust ducts checked, which
could be obstructed or inadequate for the disposal of fumes into
the atmosphere.
For the air intake / flue gas discharge, the specific ducts and
systems for original condensing boilers must be used, resistant
to the attack of condensate acids.
The exhaust pipes must be installed with a slope towards the
boiler such as to guarantee the reflux of the condensate towards
the combustion chamber which is built to collect and discharge
the condensate.
If this is not possible, it is necessary to install systems capable
of collecting and conveying the condensate to the condensate
drainage system in the condensate stagnation points.
It is necessary to avoid condensation stagnation points in the
combustion products evacuation system, with the exception
of the liquid head of any siphon connected to the combustion
products evacuation system.
The manufacturer declines all responsibility for damage caused
as a result of installation, use or transformation errors
of the appliance or for failure to comply with the instructions
provided by the manufacturer or the installation standards in
force concerning.
External booster
Indoor unit
Per il posizionamento a parete dei terminali di scarico della
caldaia, nei casi prescritti dal DPR n.551 del 29/12/99, attenersi
alle distanze di cui alla tabella e alla figura che seguono.
Terminal block
Liquid line connection
Gas line connection
Pressure point R410A
R410A taps
STC
thermal probe
compressor
C
compressor
1
reversing valve
2
fan
L - N
Power supply
single phase
LEGEND: A
Air intake -
S
Fumes exhaust - Condensation -
Rain