Above
Air
™
MissionCritical
™
A/C’s
AboveAir
Technologies
(MC22-L12)
7
Performance Data
Performance Data (
MC™
2x2)
-
DX - Glycol Cooled (1-3 Tons)
Nominal Size
1.0 Tons
1.5 Tons
2.0 Tons
2.5 Tons
3.0 Tons
DX - Glycol Cooled Model
VCG-012
VCG-018
VCG-024
VCG-030
VCG-036
GLYCOL
COOLED
DX
75°F DB / 62.5°F WB, 50% RH
Total
BTUH
15,100
19,900
26,200
31,300
38,100
Sensible
BTUH
11,400
15,500
22,300
27,000
33,500
72°F DB / 60°F WB, 50% RH
Total
BTUH
14,400
18,900
24,800
29,800
36,400
Sensible
BTUH
11,200
15,200
21,800
26,700
33,400
70°F DB / 58.5°F WB, 50% RH
Total
BTUH
13,900
18,300
23,700
29,000
35,400
Sensible
BTUH
11,000
14,900
21,300
26,200
32,800
75°F DB / 61°F WB, 45% RH
Total
BTUH
14,700
19,400
25,200
29,900
37,100
Sensible
BTUH
12,100
16,800
24,600
29,200
36,100
72°F DB / 58.5°F WB, 45% RH
Total
BTUH
14,000
18,500
24,400
29,200
35,400
Sensible
BTUH
11,900
17,000
23,700
29,000
35,400
70°F DB / 57°F WB, 45% RH
Total
BTUH
13,600
18,000
23,800
28,300
34,500
Sensible
BTUH
11,700
16,800
23,700
28,300
34,500
COMPONENT DATA
GLYCOL
COOLED
DX
Reheat / Heat
-
(Standard)
Electric Reheat / Heat
- BTUH includes evaporator motor heat,
(Standard)
Capacity
BTUH (KW)
17,670 (5.2)
18,245 (5.3)
18,245 (5.3)
18,820 (5.5)
18,820 (5.5)
Hot Gas Reheat
-
(Optional)
Capacity
BTUH
13,190
16,800
24,210
27,700
32,000
Hot Water Heating Coil
-
(Optional)
@ 180°F EWT / 160°F LWT, 70°F DB EAT
Capacity
BTUH
21,760
28,080
40,540
46,910
54,640
Flow Rate / PD
GPM / FT
2.3 / (0.7)
2.9 / (1.0)
4.2 / (0.1)
4.9 / (0.2)
5.7 / (0.2)
Standard Valve
TXT
2-way - field installed
(3-way valves are optional)
Steam Canister Humidifier
-
(Standard)
Steam Canister
LBS/HR
5
5
5
5
5
Evaporator Blower / Motor
- Direct-Drive, Backward Inclined Variable Speed EC Impeller
Airflow Rate
CFM
500
750
1,000
1,250
1,600
Motor KW
KW
1.0
1.0
1.0
1.0
1.0
E.S.P.
IN WG
0.3
0.3
0.3
0.3
0.3
Motor Type
TXT
EC BI Impeller
EC BI Impeller
EC BI Impeller
EC BI Impeller
EC BI Impeller
Evaporator Coil
- Aluminum Fin, Copper Tube
Rows/Face Area
NO / FT
2
3 / 3.23
3 / 3.23
3 / 3.23
3 / 3.23
3 / 3.23
Filters
- 2", 30% Dust Spot Efficient
Up-Flow Filters
(NO) IN
(1) 18 x 24 x 2
(1) 18 x 24 x 2
(1) 18 x 24 x 2
(1) 18 x 24 x 2
(1) 18 x 24 x 2
Down-Flow Filters
(NO) IN
(1) 20 x 20 x 2
(1) 20 x 20 x 2
(1) 20 x 20 x 2
(1) 20 x 20 x 2
(1) 20 x 20 x 2
Compressor
- Heat Pump Duty, SCROLL
Qty., Nom. Tons
(NO) Tons
(1) 1.33
(1) 1.5
(1) 2.0
(1) 2.5
(1) 3.0
Glycol Cooled Condenser Data -
110°F EGT / 120°F LGT, 40% Ethylene Glycol Solution
(rated at 75°F DB/62.5°F WB EAT Cooling Performance)
Total Heat of Rej.
BTUH
20,935
26,905
34,390
41,325
50,700
Flow 110°F EGT
GPM
4.6
6.0
7.6
9.1
11.2
Pressure Drop
FT WG
8.0
11.5
11.8
15.4
17.2
Condenser Type
Coaxial
Coaxial
Coaxial
Coaxial
Coaxial
Glycol Reg. Valve
2-Way, 150 psig - factory installed,
(3-way & High Pressure Valves are Optional)
Connection Sizes
Glycol IN/OUT
OD IN
5/8
5/8
5/8
7/8
7/8
Condensate Drain
FPT IN
3/4
3/4
3/4
3/4
3/4
Humidifier Inlet
FLARE IN
1/4
1/4
1/4
1/4
1/4