Above
Air
™
MissionCritical
™
A/C’s
AboveAir
Technologies
(MC22-L12)
11
Electrical Data
Electrical Data
(
MC™
2x2)
-
Remote W/G Condensing Units
Notes:
1) FLA = Full Load Amps; MCA = Min Circuit Amps; MOP = Max Overcurrent Protection (Max Fuse Size)
2) 277/1/60 systems may require factory provided field installed step-down transformer.
3) - - - - Consult local AboveAir Sales Representative for non-cataloged system power supply information.
CWU & CGU - Indoor
Water & Glycol Cooled Remote Condensing Units
Power Supply
208/1/60 277/1/60 208/3/60 460/3/60
CWU & CGU-012
FLA
9.0
7.1
- - - -
- - - -
MCA
11.3
8.9
MOP
20
15
CWU & CGU-018
FLA
9.6
7.7
- - - -
- - - -
MCA
12.0
9.6
MOP
20
15
CWU & CGU-024
FLA
12.8
10.9
8.3
5.1
MCA
16.0
13.6
10.4
6.4
MOP
25
20
15
15
CWU & CGU-030
FLA
14.1
12.2
9.0
5.6
MCA
17.6
15.3
11.3
7.0
MOP
30
25
20
15
CWU & CGU-036
FLA
17.9
16.0
13.5
6.0
MCA
22.4
20.0
16.9
7.5
MOP
40
35
30
15
Indoor
- DX - Water / Glycol Cooled, Remote Condensing Units