![AboveAir Technologies MissionCritical MC-2x2 Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/aboveair-technologies/missioncritical-mc-2x2/missioncritical-mc-2x2_engineering-manual_3464778010.webp)
Above
Air
™
MissionCritical
™
A/C’s
AboveAir
Technologies
(MC22-L12)
10
Electrical Data
Electrical Data
(
MC™
2x2)
-
DX Air Cooled, Remote Cond Units & Conds
Outdoor, Pad Mtd - DX - Air Cooled, Remote Condensing Units & Condensers
XPU - Outdoor Propeller Fan
Air Cooled Remote Condensing Units
XP1 - Outdoor Propeller Fan
Air Cooled Remote Condensers
Power Supply
208/1/60 277/1/60 208/3/60 460/3/60
Power Supply
208/1/60 277/1/60 460/1/60
XPU-012
XP1-012
FLA
9.5
7.1
- - - -
- - - -
FLA
0.5
0.4
0.6
MCA
11.8
8.8
MCA
0.6
0.5
0.8
MOP
20
15
MOP
15
15
15
XPU-018
XP1-018
FLA
10.4
7.8
- - - -
- - - -
FLA
0.8
0.6
0.6
MCA
17.6
13.2
MCA
1.0
0.8
0.8
MOP
30
20
MOP
15
15
15
XPU-024
XP1-024
FLA
13.6
10.2
9.1
5.2
FLA
0.8
0.6
0.7
MCA
16.8
12.6
11.2
6.3
MCA
1.0
0.8
0.9
MOP
25
20
20
15
MOP
15
15
15
XPU-030
XP1-030
FLA
15.5
11.6
11.9
6.3
FLA
1.4
1.1
0.7
MCA
19.0
14.3
14.5
7.7
MCA
1.8
1.3
0.9
MOP
30
25
20
15
MOP
15
15
15
XPU-036
XP1-036
FLA
19.0
14.3
14.6
6.6
FLA
1.1
0.8
0.6
MCA
23.5
17.6
18.0
8.1
MCA
1.4
1.0
0.8
MOP
40
30
30
15
MOP
15
15
15
Indoor, Ceiling Mtd - DX - Air Cooled, Remote Condensing Units & Condensers
CCU - Indoor (Ceiling Mtd), Centrifugal Blower
Air Cooled Remote Condensing Units
CCX - Indoor (Ceiling Mtd), Centrifugal Blower
Air Cooled Remote Condensers
Power Supply
208/1/60 277/1/60 208/3/60 460/3/60
Power Supply
208/1/60 277/1/60 208/3/60 460/1/60 460/3/60
CCU-012
CCX-012
FLA
13.0
10.3
- - - -
- - - -
FLA
4.0
3.2
- - - -
1.8
- - - -
MCA
15.3
12.1
MCA
5.0
4.0
2.3
MOP
20
15
MOP
15
15
15
CCU-018
CCX-018
FLA
13.6
10.9
- - - -
- - - -
FLA
4.0
3.2
- - - -
1.8
- - - -
MCA
16.0
12.8
MCA
5.0
4.0
2.3
MOP
25
20
MOP
15
15
15
CCU-024
CCX-024
FLA
18.2
14.8
13.7
7.3
FLA
5.4
3.9
- - - -
2.2
- - - -
MCA
21.4
17.5
15.8
8.6
MCA
6.8
4.9
2.8
MOP
30
25
20
15
MOP
15
15
15
CCU-030
XCX-030
FLA
19.5
16.1
14.4
7.8
FLA
5.4
3.9
- - - -
- - - -
2.2
MCA
23.0
19.2
16.7
9.2
MCA
6.8
4.9
2.8
MOP
35
30
25
15
MOP
15
15
15
XCU-036
XCX-036
FLA
24.6
21.0
17.3
7.9
FLA
6.7
5.4
3.8
- - - -
1.9
MCA
29.1
25.0
20.7
9.4
MCA
8.4
6.8
4.8
2.4
MOP
45
40
30
15
MOP
15
15
15
15
Notes:
1) FLA = Full Load Amps; MCA = Min Circuit Amps; MOP = Max Overcurrent Protection (Max Fuse Size)
2) 277/1/60 systems may require factory provided field installed step-down transformer.
3) - - - - Consult local AboveAir Sales Representative for non-cataloged system power supply information.