73
AC grid to the converter. If the error
continues to occur, please contact the
supplier.
AL11
Insulation resistance
error
Converter DC input
insulation resistance too
low and fails to meet
specifications
1. Disconnect the solar panel array from the
converter, and disconnect the converter
from the grid.
2. Confirm that the converter DC input
terminal and the solar panel array are
normal (e.g., no short circuits, no
damaged wire insulation).
3. Re-connect the solar panel array and the
AC grid to the converter. If the error
continues to occur, please contact the
supplier.
AL25
Overtemperature
warning
Converter overtemperature
so derating mechanism is
triggered
1. Lower the ambient temperature of the
converter or relocate the converter to a
well-vented location.
2. If the error continues to occur, please
contact the supplier.
AL31
DC varistor
failure_standard
model
DC varistor function failure
Based on the code, replace the DC or AC
varistor.
AL32
AC varistor
failure_standard
model
AC varistor function failure
AL37
DC varistor
failure_model 1
DC varistor function failure
AL38
AC varistor
failure_model 1
AC varistor function failure
AL40
DC varistor
failure_model 2
DC varistor function failure
AL41
AC varistor
failure_model 2
AC varistor function failure
AL42
Input mode setting
incorrect
Converter input setting
incompatible with solar
panel
Inverter DC input is configured to
“Synchronization”, and the “A” array input
voltage of maximum power point tracker is
too low. Please confirm whether “A” array
of the solar panel array is functioning
normally.
AL43
AC switch open circuit
AC switch open circuit
Grid connection needs closed switch
Содержание EnerSolis Series
Страница 1: ...Ablerex Grid Connected Solar Converter EnerSolis Series ES 52000HC ES 60000HC User Manual ...
Страница 4: ...3 ...
Страница 9: ...8 8 AC output Transmits AC power generated from the inverter to the mains ...
Страница 13: ...12 sufficient space must be reserved for heat dissipation and installation as shown in the figure below ...
Страница 16: ...15 抓握處 Handles ...
Страница 20: ...19 Step 8 Use 4 M4 stainless steel truss head screws to secure the rain shield on the left and right sides ...
Страница 24: ...23 Figure 2 ...
Страница 27: ...26 Figure 6 Figure 4 Figure 5 ...
Страница 42: ...41 ...
Страница 47: ...46 may be incompatible with the local power system requirements or the converter may not operate properly ...
Страница 49: ...48 the RS485 port of the cloud module please refer to 6 1 Communication Interface ...
Страница 51: ...50 ...
Страница 54: ...53 ...
Страница 56: ...55 ...
Страница 60: ...59 confirm whether there is an input error ...
Страница 65: ...64 M4 stainless steel screw x4 ...